51
Replacement Checklists
Section 3-6
Level/Link
Number
Check setting on pins 3 and 4 of SW3:
[
]
Pins 3 and 4: Set the same Level/
Link Number as set on the C500-
LK009-V1.
The CVM1-LK401’s sin-
gle-level mode is equiva-
lent to the C500-LK009-
V1’s single-level LK009
mode. The CVM1-LK401
cannot emulate the sin-
gle-level LK003 mode.
Pattern A systems do not
include Units set to sin-
gle-level LK003 mode.
Pins
3 & 4
Level/Link Number setting
Pins
3 & 4
Level/Link Number set-
ting
11
Single-level LK009
11
Single-level (Either 11 or
10 can be set.)
10
Single-level LK003
10
01
Multi-level Link #1
01
Multi-level Link #1
00
Multi-level Link #0
00
Multi-level Link #0
Transmis-
sion Line
Selector
Check setting on SW2:
[
Up (4-wire)
Down (2-wire)]
WIRE switch: Set the same setting
as set on the C500-LK009-V1.
---
Up
4-wire/Use optical fiber cable.
4 (left)
4-wire/Use optical fiber
cable.
Down
2-wire/Use electrical cable.
2 (right) 2-wire/Use electrical
cable.
Terminating
Resistance
Check setting on pin 1 of SW3:
[
1(ON
)/
0 (OFF)]
TER switch: Set the same setting
as set on the C500-LK009-V1.
---
1
Terminator connected.
ON
(left)
Terminator connected.
0
Terminator not connected.
OFF
(right)
Terminator not con-
nected.
LR Area
LR 00 to LR 63
(or LR 00 to LR 31 in the C500)
CIO 1000 to CIO 1063
N is the CPU Bus Unit’s
unit number.
PC Link Error
and PLC Run
Flags
SR 247 to SR 250
(or SR 58 and SR 62 in the C500)
CIO 1500 + 25
×
N to
CIO 1500 + 25
×
N + 3
Level Flags
Level #1
AR 2411
(Except C500)
Level
#1
CIO 1500 + 25
×
N + 4,
bit 11
Single-level or level
#0
AR 2412
(Except C500)
Single-
level or
level #0
CIO 1500 + 25
×
N + 4,
bit 12
PC Link Unit
Restart Bits
Level #1
SR 25210
(SR 6010 in C500)
Corresponding bit in A001 (CPU
Bus Unit Restart Bits)
Single-level or level
#0
SR 25214
(SR 6014 in C500)
Item
Original Unit: C500-LK009-V1
Replacement Unit: CVM1-LK401
Remarks
Содержание CVM1 Series
Страница 1: ...Cat No W434 E1 01 SYSMAC CVM1 CV Series CVM1 LK401 PC Link Unit This manual is PDF file only...
Страница 2: ...CVM1 LK401 PC Link Unit Operation Manual Produced July 2004...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 41: ...26 Differences from Earlier PC Link Units Section 2 6...
Страница 77: ...62 Replacement Checklists Section 3 6...
Страница 95: ...80 Link Adapter Specifications Appendix B...
Страница 101: ...86 PC Link System I O Response Time Appendix C...
Страница 103: ...88 PC Link Settings and Status Areas Appendix D...
Страница 105: ...Revision History 90...