Link Adapter Specifications
Appendix B
Cable Length (Maximum)
APF: All Plastic Optical Fiber Cable
PCF: Plastic Clad Optical Fiber Cable
• The Link Adapter will operate with either a 100/200 VAC or 12 to 24 V (AC or DC) power supply.
• The repeater input terminals should be shorted during normal use.
Note
(1) Always short the repeater input terminals when using the Link Adapter. The Link Adapter will not
operate unless the terminals are shorted.
(2) Always place the protective caps on unused optical connectors. When the cap is not in place, it is
possible for scattered light to cause transmission errors.
(3) When the Link Adapter is installed in an office or on a desk, take steps to prevent the power supply
terminals from being touched accidentally, which can cause an electric shock.
3G2A9-AL004-(P)E Link Adapter
Dimensions
Cable type
3G2A9-AL002-PE
3G2A9-AL002-E
APF
20 m
Cannot be connected.
PCF
200 m
800 m
200
VAC
POWER
FUSE 0.3 A
100
VAC
LG
RS232C
RS422
FG
AL004
LINK ADAPTER
4.5
7
10 dia.
52.5
120
174
Approx. 140
63
188
164
Terminal block
CTS selector
switch
Terminating
resistance
selector switch
Fuse
Mounting hole
dimensions
Power indicator
Содержание CVM1 Series
Страница 1: ...Cat No W434 E1 01 SYSMAC CVM1 CV Series CVM1 LK401 PC Link Unit This manual is PDF file only...
Страница 2: ...CVM1 LK401 PC Link Unit Operation Manual Produced July 2004...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 41: ...26 Differences from Earlier PC Link Units Section 2 6...
Страница 77: ...62 Replacement Checklists Section 3 6...
Страница 95: ...80 Link Adapter Specifications Appendix B...
Страница 101: ...86 PC Link System I O Response Time Appendix C...
Страница 103: ...88 PC Link Settings and Status Areas Appendix D...
Страница 105: ...Revision History 90...