25
Function Block Specifications
Section 2-1
2.
When the instance is executed, output variables are passed to the corre-
sponding parameters after the algorithm is processed. Consequently, val-
ues cannot be written from output variables to parameters within the
algorithm. If it is necessary to write a value within the execution cycle of the
algorithm, do not write the value to a parameter. Assign the value to an in-
ternal variable and use an AT setting (specified addresses).
Initial Value
An initial value can be set for an output variable that is not being retained, i.e.,
when the Retain Option is not selected. An initial value cannot be set for an
output variable if the Retain Option is selected.
The initial value will not be written to the output variable if the IOM Hold Bit
(A50012) is ON.
ENO (Enable Output) Variable
The ENO variable is created as the default output variable. The ENO output
variable will be turned ON when the instance is called. The user can change
this value. The ENO output variable can be used as a flag to check whether or
not instance execution has been completed normally.
■
Internal Variables
Internal variables are used within an instance. These variables are internal to
each instance. They cannot be referenced from outside of the instance and
are not displayed in the instance.
The values of internal variables are retained until the next time the instance is
executed (i.e., when EN turns OFF, the value of the internal variable is
retained). Consequently, even if instances of the same function block defini-
tion are executed with the same I/O parameters, the result will not necessarily
be the same.
Example:
The internal variable tim_a in instance Pulse_2sON_1sOFF is different from
internal variable tim_a in instance Pulse_4sON_1sOFF, so the instances can-
not reference and will not affect each other’s tim_a value.
Auxiliary Area control bit
Initial value
IOM Hold Bit (A50012)
ON
The initial value will not be set.
P_On
1.0
&10
CLOCK PULSE
EN
ENO
ON_TIME
OFF_TIME
&20
Pulse_2sON_1sOFF
P_On
1.1
&10
CLOCK PULSE
EN ENO
ON_TIME
OFF_TIME
&40
Pulse_4sON_1sOFF
tim_a
TIMER
tim_b
TIMER
ON_TIME
INT
OFF_TIME
INT
Variable table
Name
Internal
Internal
Input
Input
Data type
Usage
Содержание CS1-H Series
Страница 3: ...iv...
Страница 5: ...vi...
Страница 7: ...viii TABLE OF CONTENTS...
Страница 15: ...xvi Application Precautions 4...
Страница 151: ...136 Procedures Section 3 2...
Страница 153: ...138 Data Types Appendix A...
Страница 177: ...162 External Variables Appendix C...
Страница 181: ...166 Revision History...