![Omron CS1-H Series Скачать руководство пользователя страница 122](http://html1.mh-extra.com/html/omron/cs1-h-series/cs1-h-series_operation-manual_742526122.webp)
107
CPU Unit Function Block Specifications
Section 2-7
2-7-2
Operation of Timer Instructions
There is an option called
Apply the same spec as TO-2047 to T2048-4095
in
the PLC properties of CPU Units. This setting affects the operation of timers
as described in this section.
Selecting the Option
(Default)
If this option is selected, all timers will operate the same regardless of timer
number, as shown in the following table.
Timer Operation for Timer Numbers T0000 to T4095
Not Selecting the
Option
If this option is not selected, the refreshing of timer instructions with timer
numbers T0000 to T2047 will be different from those with timer numbers
T2048 to T4095, as given below. This behavior is the same for CPU Units that
do not support function blocks. (Refer to the descriptions of individual instruc-
tion in the
CS/CJ Series Instruction Reference
for details.)
Function
blocks
Maxi-
mum
number of
definitions
128
Maxi-
mum
number of
instances
256
Flash
memory
Function
block pro-
gram
memory
(Kbytes)
256
Com-
ment files
(Kbytes)
64
Program
index files
(Kbytes)
64
Variable
tables
(Kbytes)
64
Item
Specification
Units with internal I/O functions
Units without internal I/O functions
Refresh
Description
When instruction is
executed
The PV is refreshed each time the instruction is executed.
If the PV is 0, the Completion Flag is turned ON. If it is not 0,
the Completion Flag is turned OFF.
When execution of all
tasks is completed
All PV are refreshed once each cycle.
Every 80 ms
If the cycle time exceeds 80 ms, all PV are refreshed once
every 80 ms.
Содержание CS1-H Series
Страница 3: ...iv...
Страница 5: ...vi...
Страница 7: ...viii TABLE OF CONTENTS...
Страница 15: ...xvi Application Precautions 4...
Страница 151: ...136 Procedures Section 3 2...
Страница 153: ...138 Data Types Appendix A...
Страница 177: ...162 External Variables Appendix C...
Страница 181: ...166 Revision History...