![Omron CPM2A - 11-2005 Скачать руководство пользователя страница 63](http://html1.mh-extra.com/html/omron/cpm2a-11-2005/cpm2a-11-2005_manual_742517063.webp)
!
43
CPM1A-TS101/102
Set value
Platinum resistance
thermometer
Range (
°
C)
Range (
°
F)
0
Pt100
–200.0 to 650.0
–300.0 to 1,200.0
1
JPt100
–200.0 to 650.0
–300.0 to 1,200.0
2 to F
---
Setting not possible
4. Expansion I/O Connecting Cable
Connects the Temperature Sensor Unit to the expansion connector on the
PC’s CPU Unit, an Expansion I/O Unit, or another Expansion Unit. The cable
is connected to the Temperature Sensor Unit and cannot be removed.
Caution
Do not touch the expansion I/O connecting cable while the power is being sup-
plied in order to prevent any malfunction due to static electricity.
5. Expansion Connector
Connects to an additional Expansion I/O Unit or another Expansion Unit.
2-2-5 CompoBus/S I/O Link Unit Components
1. CompoBus/S terminals
4. Expansion I/O connecting cable
2. DIP switch
5. Expansion connector
3. LED indicators
1, 2, 3...
1. CompoBus/S Terminals
Include the CompoBus/S communications data high/low terminal, commu-
nications power /– terminals, and NC terminals. Power is supplied
to the Unit internally, so the power supply terminals can be used as relay
terminals.
2. DIP Switch
The DIP switch sets the Unit’s node address, sets the communications
mode, and determines whether or not the outputs will be cleared in the event
of a communications error.
Pin(s)
Function
1 to 4
(labeled
1, 2, 4,
and 8)
These pins set the Unit’s node address using the DIP switch pins as
binary digits. (1 = ON)
0: 0000
1: 0001
2: 0010
3: 0011
4: 0100
5: 0101
6: 0110
7: 0111
8: 1000
9: 1001
10: 1010
11: 1011
12: 1100
13: 1101
14: 1110
15: 1111
DR
ON: Long-distance Communications Mode
OFF: High-speed Communications Mode
(See note.)
HOLD
ON: Retain outputs when a communications error occurs.
OFF: Clear outputs when a communications error occurs.
Note
The Long-distance Communications Mode can be used only when connected to
one of the following Master Units: C200HW-SRM21-V1, CQM1-SRM21-V1, or
SRM1-C0
j
-V2.
Unit Components
Section 2-2
NODE ADDRESS
1
2
4
8
DR
HOLD
SW1
ON
Содержание CPM2A - 11-2005
Страница 1: ...OPERATION MANUAL Programmable Controllers SYSMAC CPM2A Cat No W352 E1 07...
Страница 2: ...CPM2A Programmable Controllers Operation Manual Revised November 2005...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 12: ...xiv...
Страница 179: ...Appendix B Dimensions 164 CPM1 CIF11 RS 422 Adapter...