4-2
Section
Programming Console Operations
108
Program Read then Monitor
When a program address is being displayed, the status of the bit or word in that
address can be monitored by pressing the MONTR Key.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the desired program address and press the Down Arrow Key.
C
2
A
0
A
0
↓
00200READ
TIM 000
3. Press the MONTR Key to begin monitoring.
MONTR
T000
1234
If the status of a bit is being monitored, that bit’s status can be changed using
the Force Set/Reset operation. Refer to
4-2-26 Force Set, Reset
for details.
If the status of a word is being monitored, that word’s value can be changed
using the Hexadecimal/BCD Data Modification operation. Refer to
4-2-22
Hexadecimal, BCD Data Modification, 4-2-23 Binary Data Modification,
4-2-24 Signed Decimal Data Modification,
and
4-2-25 Unsigned Decimal
Data Modification
for details.
4. Press the CLR Key to end monitoring.
CLR
00200
TIM 000
Bit Monitor
Follow the procedure below to monitor the status of a particular bit.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the bit address of the desired bit and press the MONTR Key.
SHIFT
CONT
#
B
1
MONTR
00001
^ ON
The Up or Down Arrow Key can be pressed to display the status of the pre-
vious or next bit.
The displayed bit’s status can be changed using the Force Set/Reset opera-
tion. Refer to
4-2-26 Force Set, Reset
for details.
3. Press the CLR Key to end monitoring.
CLR
00000
CONT 00001
Word Monitor
Follow the procedure below to monitor the status of a particular word.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the word address of the desired word.
SHIFT
CH
*DM
LR
*EM
B
1
00000
CHANNEL LR 01
3. Press the MONTR Key to begin monitoring.
MONTR
cL01
FFFF
The Up or Down Arrow Key can be pressed to display the status of the pre-
vious or next word.
The displayed word’s status can be changed using the Hexadecimal/BCD
Data Modification operation. Refer to
4-2-22 Hexadecimal, BCD Data Modi-
fication, 4-2-23 Binary Data Modification, 4-2-24 Singed Decimal Data Mod-
ification,
and
4-2-25 Unsigned Decimal Data Modification
for details.
Содержание CPM2A - 11-2005
Страница 1: ...OPERATION MANUAL Programmable Controllers SYSMAC CPM2A Cat No W352 E1 07...
Страница 2: ...CPM2A Programmable Controllers Operation Manual Revised November 2005...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 12: ...xiv...
Страница 179: ...Appendix B Dimensions 164 CPM1 CIF11 RS 422 Adapter...