Programming Console Operations
114
This operation can be used to increment and decrement an SV constant. It is
possible only when the SV has been entered as a constant.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Display the desired timer or counter.
TIM
SRCH
00201SRCH
TIM 000
3. Press the Down Arrow, CHG, and then the EXT Key.
↓
CHG
EXT
00201DATA ? U/D
T000 #0123 #0123
The constant on the left is the old SV and the constant on the right will be-
come the new SV constant in step 5.
4. Press the Up and Down Arrow Keys to increment and decrement the con-
stant on the right. (In this case the SV is incremented once.)
↓
00201DATA ? U/D
T000 #0123 #0124
5. Press the CLR Key twice to change the timer’s SV to the new value.
CLR
CLR
00201 TIM DATA
#0124
4-2-22 Hexadecimal, BCD Data Modification
This operation is used to change the BCD or hexadecimal value of a word
being monitored using the procedure described in
4-2-14 Bit, Digit, Word
Monitor
. It is possible in MONITOR or PROGRAM mode only.
RUN
MONITOR
PROGRAM
No
OK
OK
Words SR 253 to SR 255 cannot be changed.
Caution
Before changing the contents of I/O memory, be sure that the changes will not
cause equipment to operate unexpectedly or dangerously. In particular, take
care when changing the status of output bits. The PC continues to refresh I/O
bits even if the PC is in PROGRAM mode, so devices connected to output points
on the CPU Unit, Expansion Units, or Expansion I/O Units may operate unex-
pectedly.
1, 2, 3...
1. Monitor the status of the desired word according to the procedure described
in
4-2-14 Bit, Digit, Word Monitor
. If two or more words are being monitored,
the desired word should be leftmost on the display.
(Word monitor)
D0000
0119
2. Press the CHG Key to begin hexadecimal, BCD data modification.
CHG
PRES VAL?
D0000 0119 ????
3. Input the new PV and press the WRITE Key to change the PV.
The operation will end and the normal monitoring display will return when
the WRITE Key is pressed.
C
2
A
0
A
0
WRITE
D0000
0200
Incrementing and
Decrementing a Constant
Содержание CPM2A - 11-2005
Страница 1: ...OPERATION MANUAL Programmable Controllers SYSMAC CPM2A Cat No W352 E1 07...
Страница 2: ...CPM2A Programmable Controllers Operation Manual Revised November 2005...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 12: ...xiv...
Страница 179: ...Appendix B Dimensions 164 CPM1 CIF11 RS 422 Adapter...