The CPM2A CPU Unit can be connected to a Programming Console or a host
computer running CX-Programmer, SYSMAC Support Software (SSS), or SYS-
MAC-CPT Support Software.
The CPM2A CPU Unit can be connected to a C200H-PRO27-E Programming
Console with a standard C200H-CN222 (2 m) or C200H-CN422 (4 m) Connect-
ing Cable. The CPM2A CPU Unit can be also connected to a CQM1-PRO01-E.
A 2-m Connecting Cable is attached to the CQM1-PRO01-E.
CQM1-PRO01-E Connection
CQM1-PRO01-E
CPM2A CPU Unit
Peripheral port
C200H-PRO27-E Connection
C200H-PRO27-E
Connecting Cable
C200H-CN222 (2 m)
C200H-CN422 (4 m)
CPM2A CPU Unit
Peripheral port
Connect the Programming Console to the CPU Unit’s Peripheral port; a Pro-
gramming Console cannot be connected to the RS-232C port. The PC will auto-
matically communicate with the Programming Console in Programming Con-
sole mode, regardless of the communications method selected on the CPU
Unit’s Communications Switch.
An IBM-compatible personal computer running the SSS or CX-Programmer and
SYSMAC-CPT Support Software can be connected to the CPU Unit’s Peripher-
al port or RS-232C port. The Peripheral port can operate in Peripheral bus mode
or Host Link mode. The RS-232C port operates in Host Link mode only.
The setting on the CPU Unit’s Communications Switch determines whether the
RS-232C port will operate with the communications settings in the PC Setup or
the standard settings, as shown in the following table.
Switch
i
Communications settings
setting
Peripheral port
RS-232C port
ON
Standard settings (The standard settings and PC Setup default settings
are Host Link communications at 9,600 bps with 1 start bit, 7-bit data, 2
stop bits, and even parity.)
OFF
PC Setup settings in DM 6650 and
DM 6651
PC Setup settings in DM 6645 and
DM 6646
Connect to the Peripheral port when connecting to the PC’s Peripheral bus. The
communications mode will be Host Link communications, but the CPM2A will
automatically switch to Peripheral bus communications if Peripheral bus has
been selected in the Support Software.
Programming Console
Support Software
Wiring and Connections
Section 3-4
Содержание CPM2A - 11-2005
Страница 1: ...OPERATION MANUAL Programmable Controllers SYSMAC CPM2A Cat No W352 E1 07...
Страница 2: ...CPM2A Programmable Controllers Operation Manual Revised November 2005...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 12: ...xiv...
Страница 179: ...Appendix B Dimensions 164 CPM1 CIF11 RS 422 Adapter...