3-29
3 Operation and Configuration
CJ-series High-speed Counter Units Operation Manual for NJ-series CPU Unit(W492)
3-5 Outp
ut Con
tr
o
l
3
3-5-2 C
o
mpar
ison Mode
Additional Information
The Counter Output Patterns of Counters which are configured to use no (i.e. zero) Ranges, are
ignored in the AND-calculation of the Unit Output Pattern. Like this, Counters that you do not
want to use, do not influence the AND-calculation of the Unit Output Pattern. If both the Counters
are configured to use no Ranges, the output patterns for both outputs will be all OFF.
If the Unit is configured to control the Outputs in Comparison Mode, this Mode can be applied to Circu-
lar Counters or Linear Counters (refer to 3-2-2 Circular Counter and 3-2-3 Linear Counter for more
information).
Name of device variable
for CJ-series Unit
Type
Name
Function
*_OutCtlMdCfg
WORD
Output Control
Mode/AND/OR
Counter Output
Patterns
Bits 0 to 7: Output Control Mode
Sets the Output Control Mode.
16#00: Range Mode
16#01: Comparison Mode
Bits 8 to 15: Counter output pattern AND/OR
selection
For Range Mode, selects whether the
Counter output pattern is logically OR or
AND.
16#00: OR
16#01: AND
3-5-2
Comparison Mode
Содержание CJ1W-CT021
Страница 10: ...Manual Structure 8 CJ series High speed Counter Units Operation Manual for NJ series CPU Unit W492...
Страница 38: ...Revision History 36 CJ series High speed Counter Units Operation Manual for NJ series CPU Unit W492...
Страница 190: ...Appendicies A 18 CJ series High speed Counter Units Operation Manual for NJ series CPU Unit W492...
Страница 191: ...Index 1 CJ series High speed Counter Units Operation Manual for NJ series CPU Unit W492 I Index...
Страница 194: ...Index 4 CJ series High speed Counter Units Operation Manual for NJ series CPU Unit W492 Index...
Страница 195: ......