4-17
4 Exchanging Data with CPU
CJ-series High-speed Counter Units Operation Manual for NJ-series CPU Unit(W492)
4-2 Mem
o
ry
Alloca
tion
4
4-2-4 D
e
tails of De
vice V
a
riab
les
for CJ-ser
ies Unit (f
or setting)
*_NoiseFltCntCfg
UINT
R/W
Input Noise Filter
Counters
Selects the Counter 1 and 2 noise filter.
0: 50 kHz (factory value)
1: 500 kHz
2: 10 kHz
*_NoiseFltInCfg
UINT
R/W
Input Noise Filter
Digital Inputs
Selects the Digital Input 0 and 1 noise filter.
0: 50 kHz (factory value)
1: 10 kHz
*_OutOnDelayTm0Cfg
WORD
R/W
Output Pulse Turn ON-
Delay Time (BCD) Dig-
ital Output 0
Sets the output pulse turn ON-delay time for exter-
nal output 0 as a BCD.
When you set this to 16#0000, the status is normal
functions.
Data range: 16#0000 to 9999
Unit: ms
Factory value: 16#0000
*_OutDur0Cfg
WORD
R/W
Output Pulse Duration
(BCD) Digital Output 0
Sets the output pulse duration for external output 0
as a BCD.
When you set this to 16#0000, the status is normal
functions.
Setting this to 16#0000 disables this function.
Data range: 16#0000 to 9999
Unit: ms
Factory value: 16#0000
*_OutOnDelayTm1Cfg
WORD
R/W
Output Pulse Turn ON-
Delay Time (BCD) Dig-
ital Output 1
Sets the output pulse turn ON-delay time for exter-
nal output 1 as a BCD.
When you set this to 16#0000, the status is normal
functions.
Data range: 16#0000 to 9999
Unit: ms
Factory value: 16#0000
*_OutDur1Cfg
WORD
R/W
Output Pulse Duration
(BCD) Digital Output 1
Sets the output pulse duration for external output 1
as a BCD.
When you set this to 16#0000, the status is normal
functions.
Setting this to 16#0000 disables this function.
Data range: 16#0000 to 9999
Unit: ms
Factory value: 16#0000
Name of device variable
for CJ-series Unit
Type
R/W
Name
Function
Содержание CJ1W-CT021
Страница 10: ...Manual Structure 8 CJ series High speed Counter Units Operation Manual for NJ series CPU Unit W492...
Страница 38: ...Revision History 36 CJ series High speed Counter Units Operation Manual for NJ series CPU Unit W492...
Страница 190: ...Appendicies A 18 CJ series High speed Counter Units Operation Manual for NJ series CPU Unit W492...
Страница 191: ...Index 1 CJ series High speed Counter Units Operation Manual for NJ series CPU Unit W492 I Index...
Страница 194: ...Index 4 CJ series High speed Counter Units Operation Manual for NJ series CPU Unit W492 Index...
Страница 195: ......