Unit Settings
Section 5-1
52
5-1
Unit Settings
This Special I/O Unit is configurable with settings made in a dedicated DM
area. The assigned DM area depends on the Unit number setting.
The first word in the DM area allocated to the unit will be indicated by DM m,
the last word by DM m+17.
The Unit settings determine the areas and methods for data exchange
between the PLC CPU and the C200HW-PRM21.
Data entered in the Unit settings area is only transferred to the unit during
initialisation, i.e. at power ON and at Special I/O Unit restart.
Note
The Unit operates in default mode when all Unit settings are set to zero.
5-1-1
I/O Data Mapping
Data flow
I/O refresh
The figure below shows the flow of remote I/O data in the PLC system. It is
possible to map the I/O data to the DM, LR, IR and HR areas of the PLC
memory. Up to two input areas and two output areas may be assigned.
Output data is transferred via the bus on the Backplane (I/O Bus) to the
output buffer of the Unit. At certain time intervals this data is transmitted to the
slaves over PROFIBUS. Slave input data coming from PROFIBUS is first
stored in the input buffer of the Unit. At certain times, this data is transferred
to the memory of the PLC. The exchange of data via the I/O Bus occurs
during an I/O refresh.
By default, I/O refreshes are executed at the end of each PLC program cycle,
but can also be triggered by the IORF instruction.
Unit
number
DM area*
0
DM1000 ~ DM1017
1
DM1100 ~ DM1117
2
DM1200 ~ DM1217
3
DM1300 ~ DM1317
4
DM1400 ~ DM1417
All PLC models
5
DM1500 ~ DM1517
6
DM1600 ~ DM1617
7
DM1700 ~ DM1717
8
DM1800 ~ DM1817
9
DM1900 ~ DM1179
A
DM2000 ~ DM2017
B
DM2100 ~ DM2117
All PLC models except:
C
DM2200 ~ DM2217
C200HS, C200HE,
D
DM2300 ~ DM2317
C200HG-CPU3[ ]-E/CPU4[ ]-E,
E
DM2400 ~ DM2417
C200HX-CPU3[ ]-E/CPU4[ ]-E
F
DM2500 ~ DM2517
* Alternatively starting at DM7000 ~ DM8500, selected by PLC setup of C200H..:
DM6602
≠
0000 (see Operation Manual of CPU unit)
Содержание C200HW-PRM21
Страница 1: ...C200HW PRM21 PROFIBUS DP Master Unit OPERATION MANUAL Cat No W349 E2 2...
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 5: ...C200HW PRM21 PROFIBUS DP Master Unit Operation Manual Produced May 2000...
Страница 6: ...iv...
Страница 8: ...vi...
Страница 12: ...x...
Страница 66: ...Debug mode Section 4 4 50...
Страница 98: ...Messages Section 6 4 82...
Страница 108: ...Maintenance Section 7 3 92...
Страница 110: ...94...
Страница 112: ...96...
Страница 116: ...100...
Страница 120: ...104...
Страница 124: ......
Страница 126: ...Authorised Distributor Cat No W349 E2 2 Note Specifications subject to change without notice Printed in the Netherlands...