Overall Specifications
Section 3-1
18
3-1
Overall Specifications
C200HS
C200HE/HG/HX, CS1
Model code
C200HW-PRM21
Maximum. number of Master
Units
(with user defined I/O mapping)
10
C200HE-CPU11/32/42
C200HG-CPU33/43
C200HX-CPU34/44
10
C200HG-CPU53/63
C200HX-CPU54/64
CS1-series
16
Master Unit mounting position
CPU Rack or Expansion I/O Rack (classified as Special I/O Unit)
Unit cannot be mounted to SYSMAC BUS Slave Racks.
Unit cannot be used on a C200H PLC system.
Settings
Rotary switch : Unit number
Toggle switch : Bus termination
Displays
Unit status
: RUN (green LED), ERR (red LED)
Network status : READY (green LED), COMM (green LED),
NW-ST (green LED), DP-ERR (red LED)
External connectors
9-pin female sub-D connector (fieldbus connector, RS-485)
9-pin female sub-D connector (configurator connector, RS-232C)
No. of IR words
2 words of control data out + 3 words of unit status in
No. of DM settings
18 words of unit setup information
No. of slave status words
16 words of diagnostic bits (location is user definable)
Remote I/O
communi-
cations
Max. No. of
Slaves per
Master Unit
124
Max. No. of I/O
words per
Master Unit
With default DM settings:
32 words in, 32 words out
With user defined DM settings:
80 words, in up to 4 areas
With default DM settings:
50 words in, 50 words out
With user defined DM settings:
300 words in up to 4 areas;
maximum 100 words per area
Message communications
Not supported
via IOWR / IORD instructions
PROFIBUS-DP
Baud rate
9.6 / 19.2 / 93.75 / 187.5 / 500 kbit/s,
1.5 / 3 / 6 / 12 Mbit/s
Supported
functions
as client : Data_Exchange, Slave_Diag, Set_Prm, Chk_Cfg, Global_Control
as server : Get_Master_Diag
Network configuration
Configurator program (SyCon V.1.5x) for WIN 3.x, WIN 95 and WIN NT
Current consumption
600 mA at 5 V DC (from PLC power supply)
Storage temperature
-20 to +75
°
C
Operating temperature
0 to +55
°
C
Operating humidity
10% to 90% (non-condensing)
Conformance to EMC- and
environmental standards
EN 50081-2
EN 61131-2
Weight
250 g
Содержание C200HW-PRM21
Страница 1: ...C200HW PRM21 PROFIBUS DP Master Unit OPERATION MANUAL Cat No W349 E2 2...
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 5: ...C200HW PRM21 PROFIBUS DP Master Unit Operation Manual Produced May 2000...
Страница 6: ...iv...
Страница 8: ...vi...
Страница 12: ...x...
Страница 66: ...Debug mode Section 4 4 50...
Страница 98: ...Messages Section 6 4 82...
Страница 108: ...Maintenance Section 7 3 92...
Страница 110: ...94...
Страница 112: ...96...
Страница 116: ...100...
Страница 120: ...104...
Страница 124: ......
Страница 126: ...Authorised Distributor Cat No W349 E2 2 Note Specifications subject to change without notice Printed in the Netherlands...