Communication dipswitches
/i
Note
•
When the power of the Trajexia system is turned on, the
TJ2-MC__ executes its startup sequence before it initializes
the MECHATROLINK-II bus. During this startup sequence, the
ML COM LED is off.
•
When the TJ2-MC__ initializes the MECHATROLINK-II bus
with the command
MECHATROLINK(unit,0)
, the ML COM
LED goes on.
•
When the GRT1-ML2 loses the MECHATROLINK-II communi-
cation with the master, or when the command
MECHATROLINK(unit,1)
is executed, the ML COM LED goes
off.
Dipswitch
Function
Setting
Description
1
MECHATROLINK-II
address range
ON
70 hex
−
7F hex
OFF
60 hex
−
6F hex
2
MECHATROLINK-II
bus speed
OFF
10 Mbps
1
1. Trajexia only supports 10 Mbps bus speed. Therefore always set dip-
switch 2 to OFF.
3
Frame size
OFF
32 bytes
2
2. Trajexia only supports 32-byte communication. Therefore always set dip-
switch 3 to OFF.
4
HOLD/CLEAR
ON
HOLD: All outputs hold their values
when communication is lost
OFF
CLEAR: All outputs become 0 when
communication is lost