CP CR500
30
Step 3: Input of the name plate data
Figure 6-9:
Input of name plate data
Step 4: Measurement of the capacitance (GSTgA+B mode)
Figure 6-10:
Measurement of the
capacitance (Phase A)
The capacitance per phase is 104.6 nF.
With one coil (40 H) the resonance frequency is: f
res
=
= 78.8 Hz.
1
2
π
L C
⋅
⋅ ⋅
-------------------------------