Setting Up the Test
4 Setting Up the Test
The test setup consists of the
CPC 100
and
CP TD1
test system, the
CP CR500
compensating reactor(s) and the test object itself.
4.1 First Step: Grounding
Caution:
For a safe operation make sure that all units involved and the trolley, if used, are
connected to the common equipotential ground. Use earth connection cables of
at least 6 mm² cross-section. Never operate the test setup without solid
grounding.
Connect
CPC 100
,
CP TD1
, the
CP CR500
compensating reactor(s) and the
test object as described below.
Figure 4-1:
Principle diagram of test
setup
CP TD1
CP CR500
To next
CP CR500
or to
CPC 100
dongle
12 kV
Cx
Safety
Measurement
Booster Serial
CPC 100
Modem cable