Cod. 710.0159.01.00 Rev0A – 10.2011
14 - 275
AL03
Low pressure alarm with dryer in remote OFF status or stand-by
0 = alarm detection OFF
1 = alarm detection ON
1
AL08
Refrigerant compressor thermal protection alarm delay at start
Sec
1
AL09
Refrig. compressor thermal protection Max. number of activations / hour
16
AL10
Refrigerant compressor thermal protection alarm rest after AL09
0
AL11
High temperature alarm Set point PB3 (AMBIENT)
°C/°F
bar/psi
45
AL12
High temperature Differential PB3 (AMBIENT)
°C/°F
bar/psi
5
AL13
High temperature alarm delay PB3 (AMBIENT)
Min
15
AL
Alarm
parameters
AL17
Active output contact for remote output relay
0= alarm output ON
1= alarm output OFF
0
AL18
Alarm relay polarity
0= active output close contact
1= active output open contact
0
AL19
Low temperature alarm delay PB1 (DEW POINT)
Min
5
AL20
Low temperature alarm Set PB1 (DEW POINT)
°C/°F
-1,5
AL21
Low temperature alarm differential PB1 (DEW POINT)
°C/ °F
3
AL22
High temperature alarm delay PB1 (DEW POINT)
Min
15
AL23
High temperature alarm Set point PB1 (DEW POINT)
°C/°F
35
AL24
High temperature alarm differential PB1 (DEW POINT)
°C /°F
1
AL25
High temperature alarm delay PB2 (AIR INLET)
Valid only if CF05 =1
Min
20
AL26
High temperature alarm Set point PB2 (AIR INLET)
Valid only if CF05 =1
°C/°F
60
AL27
High temperature alarm differential PB2 (AIR INLET)
Valid only if CF05 =1
°C/°F
10
AL28
High temperature alarm delay PB4 (REFRIGERANT SUCTION)
Min
20
AL29
High temperature alarm Set point PB4 (REFRIGERANT SUCTION)
°C/°F
45
AL30
High temperature alarm differential PB4 (REFRIGERANT SUCTION)
°C/°F
5
AL31
Alarm Probe PB1 - Max. number of activations / hour
5
AL32
Alarm Probe PB2 - Max. number of activations / hour (AIR INLET). Valid
only if CF05 =1
5
AL33
Alarm Probe PB3 - Max. number of activations / hour
5
AL34
Alarm Probe PB4 - Max. number of activations / hour
5
AL35
Numero massimo interventi ora allarme generico utente
5
AL36
Delay temperature alarm signalling from compressor start
Min
5
Pr2
Password
Warning for user:
It’s forbidden to modify setting parameters of the electronic controller without the
authorization of the manufacturer.
6.7
SET POINT DISPLAY
Push and release
button:
•
Lower display shows the message “SET”.
•
Upper display shows current set point value.
NOTE: Any change to the machine’s configuration parameters could be harmful to its
efficiency and therefore it must be done only in collaboration with the Manufacturer.
Содержание ESD Series
Страница 2: ...1 119...
Страница 4: ...5 119...
Страница 87: ...RU OMI 1 ON OFF 12...
Страница 88: ...1 0 1 1 OMI 5 IP 42 1 2 1 2 3 4 5 6 7 8 9...
Страница 90: ...HFC 3 0 3 1 OMI 0 C 50 C 90 12 OMI 3 2 40 1000 3 3 1 2 3 4 5 10...
Страница 91: ...4 0 1S1 ON OFF 3 3 5 0 5 1 5 2 5 3 6 6 0 SET POINT 1 DEW POINT...
Страница 92: ...6 1 HP LP CO14 6 2 ON 6 3 3 ON OFF OFF SET POINT...
Страница 93: ...6 4 15 1 ALrM 2 ALOG 3 C1Hr 4 Hot Key UPL 6 5 6 5 1 P2 P3 P4 6 5 2 1 2 AlrM 3 rSt NO 4 rSt rSt...
Страница 101: ...7 0 A B 0 C A...
Страница 102: ...8 0 8 1 TEST F 1 3 2 2 8 2 NO LOSS CONDENSATE DRAIN TEST Beko 1 2 3 BEKO DISCHARGER ALARM BEKO 250 1 0 A F...
Страница 103: ...8 3 TEST 9 0 10 0 R134a R407C R507 15 15 11 0 EN378 1...
Страница 115: ...Components layout Layout componenti Lista de components Baugruppenanordnung Maquette des composants...
Страница 122: ......