Cod. 710.0159.01.00 Rev0A – 10.2011
15 - 275
6.8
SUGGESTED MAINTENANCE FUNCTION
The electronic controller is set through the CO14 “Refrigerant Compressor hour counter set” parameter. This will advise the operator
that preventive maintenance of the dryer is required (according to CAP. 5.0) every 3000 operation hours (the icon
+ AMnC alarm
code are blinking). This alarm WILL NOT STOP THE AIR DRYER WORKING. The alarm disappears after resetting the hour counter
from the Functions Menu.
Display Refrigerant Compressor working hours
1) Enter the Functions Menu (
button).
2) Push
or
buttons until the lower display will show the label “C1Hr” (refrigerant compressor working hours). Upper display
shows the number of working hours. The icon
will be on.
Reset Refrigerant Compressor working hours
1) Enter the Functions Menu (
button).
2) Push
or
buttons until the lower display will show the label “C1Hr” (refrigerant compressor working hours). Upper display
shows the number of working hours.
3) Push
button for more than 3 sec. so the upper display will show “0” confirming the reset.
4) Quit the Functions menu pushing
button or wait 15 sec. (automatic quit).
6.9
BLACK OUT
After a power black-out:
1. The controller restarts from the previous status.
2. All the working time delay will be reloaded.
6.10
REMOTE CONTROLS
6.10.1 Remote ON/OFF
The dryer can be remotely started and stopped (REMOTE ON/OFF). Proceed as follow to activate this function:
1. Disconnect the dryer from electrical supply and open the electrical box.
2. Remove the bridge between the two terminal blocks marked with “ON/OFF” (See electric wiring diagram – wires 14 and 10).
3. Connect the “ON/OFF” terminal blocks to remote a unipolar switch.
Remote ON/OFF digital input is configured as follow: close contact = dryer ON.
When the dryer is switched off using remote OFF command, the controller shows on upper display line
the message “OFF” and the remote ON/OFF led blinks.
The remote OFF function disables the ON function from the dryer’s control board (until the ON function
is activated from remote ON/OFF switch). To restart the dryer it’s necessary to operate on the remote
control.
The activation of the above function is at the user’s discretion. The user will purchase all necessary
installation materials himself. Any operation which needs access to the dryer must be carried out by
qualified personnel.
6.10.2 Remote signalling alarm
The dryer control board is supplied complete with a digital output configured as remote signalling alarm. This digital output is controlled
by a relays configured as normally open: when an alarm is detected, these relays close a circuit. The status of the relays can be
inverted, if necessary, using AL18 programming parameter (See 6.6.2 Parameters table).
Proceed as follows to activate a remote alarm output:
1. The User must provide a signaller in compliance to output relays electrical features (solenoid coil, light bulb, acoustic signaller,
...).
2. Disconnect the dryer from the electrical supply and open the electrical box.
3. Connect the signaller on “REMOTE ALARM” terminal blocks (See electric wiring diagram – wires 25 and 26).
The activation of the above function is at the user’s discretion. The user will purchase all necessary
installation materials himself. Any operation which needs access to the dryer must be carried out by
qualified personnel.
Alarm Output relays electric features:
Voltage
on User’s discretion
max. current
3A
Содержание ESD Series
Страница 2: ...1 119...
Страница 4: ...5 119...
Страница 87: ...RU OMI 1 ON OFF 12...
Страница 88: ...1 0 1 1 OMI 5 IP 42 1 2 1 2 3 4 5 6 7 8 9...
Страница 90: ...HFC 3 0 3 1 OMI 0 C 50 C 90 12 OMI 3 2 40 1000 3 3 1 2 3 4 5 10...
Страница 91: ...4 0 1S1 ON OFF 3 3 5 0 5 1 5 2 5 3 6 6 0 SET POINT 1 DEW POINT...
Страница 92: ...6 1 HP LP CO14 6 2 ON 6 3 3 ON OFF OFF SET POINT...
Страница 93: ...6 4 15 1 ALrM 2 ALOG 3 C1Hr 4 Hot Key UPL 6 5 6 5 1 P2 P3 P4 6 5 2 1 2 AlrM 3 rSt NO 4 rSt rSt...
Страница 101: ...7 0 A B 0 C A...
Страница 102: ...8 0 8 1 TEST F 1 3 2 2 8 2 NO LOSS CONDENSATE DRAIN TEST Beko 1 2 3 BEKO DISCHARGER ALARM BEKO 250 1 0 A F...
Страница 103: ...8 3 TEST 9 0 10 0 R134a R407C R507 15 15 11 0 EN378 1...
Страница 115: ...Components layout Layout componenti Lista de components Baugruppenanordnung Maquette des composants...
Страница 122: ......