Cod. 710.0103.01.00 Rev2A – 11.2012
13 - 111
CF12
ID1 digital input polarity (1S2)
0 = active with close contact
1 = active with open contact
1
CF
CF13
ID2 digital input polarity (REMOTE ON/OFF)
0 = active with close contact
1 = active with open contact
1
Configuration
Parameters
CF14
ID3 digital input polarity (1P1)
0 = active with close contact
1 = active with open contact
1
CF15
ID4 digital input polarity
0 = active with close contact
1 = active with open contact
0
CF16
ID5 digital input polarity (1Q2 – FAN THERMAL PROTECTION)
0 = active with close contact
1 = active with open contact
1
CF19
PB4 polarity (REFRIGERANT CIRCUIT SUCTION)
0 = active with close contact
1 = active with open contact
1
CF20
Condensate drain valve/s relais polarity(RL4)
0 = active with close contact
1 = active with open contact
0
CF22
Refrigerant pressure value = 4ma
bar
0
CF23
Refrigerant pressure value = 20ma
bar
30
CF24
PB1 probe calibration offset (DEW POINT)
°C/°F
-1
CF25
PB2 probe calibration offset (COMPRESSOR OIL)
°C/°F
0
CF26
PB3 probe calibration offset (AMBIENT)
°C/°F
0
CF27
PB4 probe calibration offset (REFRIGERANT CIRCUIT SUCTION)
°C/°F
0
CF28
Condensate drain unit operation
0 = Always ON
1 = Timed
1
CF29
Condensate drain ON - time
Sec
3
CF30
Condensate drain OFF - time
Sec
60
CF32
Selection: °C or °F
0 = °C / BAR
1 = °F / psi
0
CF33
Selection of mains frequency
0 = 50 Hz
1 = 60 Hz
2 = Direct current
2
CF34
Serial address
1
CF35
Remote controller
0 = 4 buttons
1 = 6 buttons
2 = 6 buttons with NTC probe on board
1
CF36
Default controller display
0 = IN / PROBE
1 = OUT / PROBE
2 = IN / rtC
3 = OUT / rtc
0
CF37
Firmware release
2.0
CF38
EEprom parameters map
1
Pr2
Password
CO01
Minimum delay at compressor re-start
sec 10x
18
CO02
Minimum delay for compressor stop
sec10x
18
CO
CO05
Delay at Refrigerant Compressor start form Power ON
min10x
48
Refrigerant
compressor
CO12
Refrigerant Compressor 1
0 = ON
1 = OFF
0
parameters
CO14
Refrigerant Compressor hour counter SET (SUGGESTED
MAINTENANCE)
h 10x
0
CO17
Difference between oil compressor and ambient temperature
°C/°F
5
Pr2
Password
FA
N.U.
---
---
AL01
Digital input low pressure alarm delay
Sec
5
AL02
Low pressure digital input Max. number of activations / hour
5
Содержание ED Series
Страница 2: ...1 113...
Страница 4: ...5 113...
Страница 82: ...Cod 710 0103 01 00 Rev2A 11 2012 78 111 RU OMI 1 ON OFF 12...
Страница 83: ...Cod 710 0103 01 00 Rev2A 11 2012 79 111 1 0 1 1 OMI IP 42 1 2 1 2 3 4 5 6 7 8 9...
Страница 85: ...Cod 710 0103 01 00 Rev2A 11 2012 81 111 HFC 3 0 3 1 OMI 0 C 50 C 90 12 OMI 3 2 20 500 3 3 1 2 3 4 10...
Страница 86: ...Cod 710 0103 01 00 Rev2A 11 2012 82 111 4 0 1S1 ON OFF 3 3 5 0 5 1 5 2 5 3 6 6 0 SET POINT 1 DEW POINT...
Страница 96: ...Cod 710 0103 01 00 Rev2A 11 2012 92 111 C A 8 0 8 1 TEST F 8 2 NO LOSS CONDENSATE DRAIN TEST Beko F...
Страница 115: ...Cod 710 0103 01 00 Rev2A 11 2012 111 111 SLI VB SC FF VG IM TH G VT...
Страница 116: ......