49
Appendix
Section Nine
FACTORY SETTINGS
LVU700 series
Sensor Height
Fill-Height
LVU706 Series
236.2” (600 cm)
228.2” (579.7 cm)
LVU712 Series
472.4” (1200 cm)
454.4” (1154.3 cm)
USER SETTINGS
Fill out the chart below and keep as a record of your configuration.
Tank
Height =
Fill-H =
Units
Inches
Feet
cm
Meter
Display
Air
Liquid
Safe
22mA
21 mA
20mA
Hold Last
4mA
Rev mA
4mA @ Bottom
4mA at Top
Start-up
4mA
12mA
20mA
22mA
TROUBLESHOOTING
PROBLEM
SOLUTION
No Unit Detected in
LVCN414-SW software.
If LVCN414-SW software cannot detect LVU700 series when connected to the
computer:
Check that the LVU500-USB Fob is connected to the USB
®
port.
Check that all four wires (Red, Black, White and Green) are securely
attached to the Fob.
Check Device Manager and confirm that both drivers (LVCN414-SW
software Configuration & EchoFob) are present.
If the above do not work, reinstall the LVCN414-SW software while the
computer is in Safe Mode.
Internet error. The server
name or address could not
be resolved.
This is a warning indicating that the computer configuring LVU700 series is not
connected to the Internet. Click
OK
to continue. OMEGA ENGINEERING
recommends being connecting to the Internet during configuration. But, not
being connected to the Internet will not prevent LVU700 series from being
configured.
Содержание LVU-700
Страница 1: ...1...
Страница 2: ...2...
Страница 6: ...6 Introduction continued Step One DIMENSIONS Dimensions for LVU706 Series Dimensions for LVU712 Series...
Страница 51: ...51...
Страница 52: ...52...