23
Configuration Using Display
Step Four
LVU700 series can be configured before installation. The transmitter features non-volatile memory, so any
setting configured before installation will not be lost when the switch is powered down. To configure, follow the
steps below:
1. Measure the Tank
a. Begin by measuring the key tank and fitting dimensions.
b. Correct tank dimensions will result in accurate sensor measurement.
2. Set the Units of Measurement (
UNITS
)
a. Units can be configured in basic engineering units of length including Feet, Inches, Centimeters
or Meters.
3. Set the Sensor Height (
HEIGHT
)
a. This is the empty setting (4mA) for the tank.
4. Set the Fill-Height (
FILL-H
)
a. This is the full setting (20mA) for the tank.
5. Set the Fail-Safety (
SAFE
)
a. This is the maximum measurement range for the sensor. The sensor will ignore all echo returns
beyond this setting.
NOTE:
When configuring LVU700 series, choose either the LVCN414-SW software or Push Button method. Either
method will accomplish the goal of sensor configuration. Changes to the configuration can be made using the
alternative method. When beginning with one method, it is recommended to complete the configuration before using
the other method to make any adjustments.