26
Configuration Using Display
(continued)
Step Four
STEP 3 - SETTING THE HEIGHT (SENSOR HEIGHT)
1. In TOP-LEVEL MENU mode, select
TANK
.
2. Select
HEIGHT
.
3. Using the UP and DOWN buttons, set the
HEIGHT
of
the tank (transducer face to the bottom of the tank).
4. To enter the value, press and hold OK for 3 seconds
and release.
SAVED
will display.
5. Select
EXIT
to return to TOP-LEVEL MENU.
Note:
The
HEIGHT
setting also determines the 4 mA current location. To reverse the current output with
20mA at the bottom of the tank, use the
REV MA
function.
Note:
To speed up the scrolling of the values on the display, hold down the OK button while holding down the
UP or DOWN buttons.