DP6060 Dual-Input Process Meter
Instruction Manual
18
Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to maintain Type 4X
rating: 0.06" (1.5 mm) steel panel, 0.16" (4.1 mm) plastic panel.
Remove the two mounting brackets provided with the meter (back-off the two
screws so that there is ¼" (6.4 mm) or less through the bracket. Slide the
bracket toward the front of the case and remove).
Insert meter into the panel cutout.
Install mounting brackets and tighten the screws against the panel. To
achieve a proper seal, tighten the mounting bracket screws evenly until
meter is snug to the panel along its short side. DO NOT OVER TIGHTEN,
as the rear of the panel may be damaged.
Figure 1. 1/8 DIN Panel Cutout Dimensions
Panel
Gasket
Mounting
Bracket
Mounting
Screw
Removable
Connectors
Figure 2. Panel Mounting Details
3.622" (92 mm)
1.772"
(45mm)
Panel Cutout
to DIN 43700
Square Corners to 0.060"
(1.5mm) Max Radius
A
B
Tolerances:
A: +0.032 (+0.8mm)
-0.000 (-0.0mm)
B: +0.024 (+0.6mm)
-0.000 (-0.0mm)