Configuration and Programming 

4.6

 

PID Control 

PID control mode is required for Ramp and Soak applications or for finer process control. For Mechanical 
Relay and SSR outputs, the output will be on a percentage of time based on the PID control values. The 
frequency of switching is determined by the (

CyCL

) parameter for each output. 

For the optional analog output, the PID control changes the output to a percentage of the full scale 
selected in the (RNGE) menu.  

 

The SSR is synchronous and can only switch ON or OFF at the 0V AC. 
PID mode may cause relay chattering when used with 

StR.1

. For this reason, the cycle 

time for 

StR.1

 is limited to a minimum of 1 second. 

4.6.1

 

PID Configuration (PRoG > PId.S) 

The PID tuning parameters must be set before PID control can be used. These parameters can 
either be set by hand in the (

PRoG>PId.S>GAIN

) menu or the controller can try to determine these 

values for you using the Autotune option. 

 

4.6.2

 

Follow these steps to run an Autotune procedure: 

1.

 

Hook up the controller in its desired configuration with the inputs and outputs 
connected. 

2.

 

Set the desired Setpoint as detailed in 

Section 4.3

. 

3.

 

Set the desired output to PID mode as detailed in 

Section 4.4.

 

4.

 

Set the action (

ACtN

) parameter 

(PRoG>PID.S>ACtn)

 as detailed below. 

 

Setting 

Description 

RVRS 

Reverse: Output increases the process value 

dRCt 

Direct: Output decreases the process value 

 

5.

 

Set the Autotune Timeout (

A.to

) parameter (

PRoG>PID.S>A.to).

 

 

(A.to)

 sets the amount of time before the Autotune process gives up and times out in 

Minutes and Seconds (

MM.SS

).  Note that slowly responding systems should have a 

longer time out setting. 

6.

 

Ensure the process value is stable. If the process value is changing, the Autotune will fail. 

7.

 

Select the Autotune (

AUto

) command 

(PRoG>PID.S>AUto)

 

Confirm Autotune activation. Using return   button. 

 

The current Process value is displayed flashing. 

 

The unit optimizes the P, I, and d settings by turning the output on and measuring 
the input response. This may take several minutes depending on the system. 

 

When the 

Autotune operation completes the unit displays the message “

doNE

”.

 

8.

 

If Autotune fails an error code is displayed. Refer to the table below to determine the 
cause. 

 

Error Code  Description 

E007 

Displays if the system does not change enough within the Autotune 
timeout period. 
Check that the output is hooked up and configured correctly or 
increase the timeout. 

E016 

Displays if the signal is not stable before starting an Autotune. 
Wait for the system to stabilize before trying to Autotune again. 

E017 

Displays if the process value is beyond the setpoint. 
Adjust the Setpoint or the Action. 

 
 

 

Содержание CS8DPT

Страница 1: ...ervice 1 800 622 2378 USA Canada only Engineering Service 1 800 872 9436 USA Canada only Tel 203 359 1660 Fax 203 359 7700 e mail info omega com For Other Locations Visit omega com worldwide The infor...

Страница 2: ...RATION AND PROGRAMMING 9 4 1 PLATINUM Series Navigation 9 4 2 Selecting an Input INIt INPt 10 4 3 Set the Setpoint 1 Value PRoG SP1 10 4 4 Set up the Control Output 11 4 4 1 Select an Output Channel P...

Страница 3: ...onal safety and hazard symbols shown in the table below in accordance with 2014 35 EU Low Voltage Directive It is important to read and follow all precautions and instructions in this manual before op...

Страница 4: ...the packing list it is important to verify all equipment shipped has been delivered as shown in Figure 1 and Table 1 If there are any questions about the shipment please email or call the Customer Se...

Страница 5: ...Power Cord DM 230V 16A USA Canada Mexico Power Cord Molded 120V Italy Power Cord IT 230V 16A Continental Europe Power Cord E 10A 240V 10A Europe Power Cord E 16A 240V 16A 3 HARDWARE SETUP This section...

Страница 6: ...l communications transmit Table 5 summarizes the universal input pin assignments for different sensor inputs All sensor selections are firmware controlled and no jumper settings are required when swit...

Страница 7: ...rs R1 and R2 included in the provided Wire Kit across terminals 4 and 6 and terminals 1 and 8 respectively This allows the Bridge voltage to be measured When powering a bridge from the unit use an int...

Страница 8: ...s Output 2 3 Ethernet Port RJ45 10 100Base T Optional 4 AC Main Input Plug IEC60320 C13 Power Socket 90 to 240 Vac 50 60 Hz 5 Output 1 Relay Output 90 240 VAC 3A Max 6 Output 2 SSR Output 90 240 VAC 5...

Страница 9: ...es across a set of menu choices at a given level When changing numerical settings press the LEFT button to make the next digit one digit to the left active The RIGHT button moves across a set of menu...

Страница 10: ...all process ranges MANL Rd 1 ____ Low display reading IN 1 ____ Manual input for Rd 1 Rd 2 ____ High display reading IN 2 ____ Manual input for Rd 2 LIVE Rd 1 ____ Low display reading IN 1 ____ Live R...

Страница 11: ...ng Parameters oFF Turn off the output channel factory default PId Set the output to Proportional Integral Derivative PID Control oN oF Set the output to On Off Control Mode RtRN Set up the output for...

Страница 12: ...tion ACtN parameter PRoG PID S ACtn as detailed below Setting Description RVRS Reverse Output increases the process value dRCt Direct Output decreases the process value 5 Set the Autotune Timeout A to...

Страница 13: ...10 Volts factory default 0 5 0 to 5 Volts 0 20 0 to 20 mA 4 20 4 to 20 mA 0 24 0 to 24 mA 4 7 2 Set Mode to Retransmission Enable the output by setting the mode to Retransmission PRoG IAN 1 Mode RtRN...

Страница 14: ...r electrical equipment for measurement control and laboratory EMC Measurement Category I Category I includes measurements performed on circuits not directly connected to the Mains Supply power Maximum...

Страница 15: ...er calibration is available with adjustable gain and offset as well as ice point calibration Refer to the Platinum Series User s Manual M5451 for additional information on user calibration options Opt...

Страница 16: ...ation misapplication misuse or other operating conditions outside of OMEGA s control Components in which wear is not warranted include but are not limited to contact points fuses and triacs OMEGA is p...

Отзывы: