Configuration and Programming
4.2
Selecting an Input (INIt>INPt)
The Benchtop Digital Controller features a Universal Input. The input type is selected in the
Initialization Menu. Select the input type by navigating to the Input sub-menu (
INIt>INPt
).
Available Input types are shown in
Table 8
.
Table 8. Input Menu.
Level 2
Level 3
Level 4
Level 5
Level 6
Level 7
Description
INPt
t.C.
k
Type K thermocouple
J
Type J thermocouple
t
Type T thermocouple
E
Type E thermocouple
N
Type N thermocouple
R
Type R thermocouple
S
Type S thermocouple
b
Type B thermocouple
C
Type C thermocouple
Rtd
N.wIR
3 wI
3-wire RTD
4 wI
4-wire RTD
2 wI
2-wire RTD
A.CRV
385.1
385 calibration curve, 100 Ω
385.5
385 calibration curve, 500 Ω
385.t
385 calibration curve, 1000 Ω
392
392 calibration curve, 100 Ω
3916
391.6 calibration curve, 100 Ω
tHRM
2.25k
2250 Ω thermistor
5k
5000 Ω thermistor
10k
10,000 Ω thermistor
PRoC
4
–
20
Process input range: 4 to 20 mA
The Manual and Live Scaling submenus are the same for all process ranges.
MANL
Rd.1
____
Low display reading
IN.1
____
Manual input for Rd.1
Rd.2
____
High display reading
IN.2
____
Manual input for Rd.2
LIVE
Rd.1
____
Low display reading
IN.1
____
Live Rd.1 input, ENTER for current
Rd.2
____
High display reading
IN.2
____
Live Rd.2 input, ENTER for current
0
–
24
Process input range: 0 to 24 mA
+-10
Process input range: -10 to +10 V
+-1
Process input range: -1 to +1 V
The Type selection submenu is available for 1V, 100mV and 50mV ranges.
tYPE
SNGL*
Ground Referenced to Rtn
dIFF
Differential between AIN+ and AIN-
RtLO
Ratiometric between AIN+ and AIN-
+-0.1
Process input range: -100 to +100 mV
+-.05
Process input range: -50 to +50 mV
*SNGL selection not available for +/-0.05V range.
4.3
Set the Setpoint 1 Value (PRoG > SP1)
Setpoint 1 is the main setpoint used for control and is displayed on the front of the unit. The unit will try
to maintain the input value at the setpoint using the selected outputs.
In the program menu, using the return button, select the
SP1
parameter. Use left
and right
buttons to set the process goal value for
PID
and
oN.oF
control modes.
Refer to
Section 4.5
Section 4.6
for more information on setting up control modes.