6.6.6
Function [46]
Rate (99.99) minutes
The Rate function allows the operator to examine and change the
differential function of PID control.
In function [46] function display will show 46, the zone display will be
blank, and the upper display will show the current Rate.
To increment the flashing digit press the button
To advance to the next digit press the button
To save setting and exit to function [73] press the button
6.6.7
Function [47]
enable Cooling zone
This function is set in the same manner as function [43].
Zones enabled by this function will run in on / off control mode and will
have outputs inverted to control cooling.
6.7 Function [74] Segment Control (set number
of Profile Segments for each zone)
The segments function allows the operator to set the size of the profile in
segments and the number of profile variants. Function [74] does not
control any other function
On entering function [74] function display shows 74.
Zone display shows zone 1.
The first and second digits in the upper display shows the current
number of segments for the displayed zone.
To increment the flashing digit press the button
To advance to the next digit press the button
To save the settings and go to the next zone press the button
To exit to function [70] use the buttons and
together
for a few seconds.
Note !! The number of segments is restricted to 20 for each zone.
Setting 0 segments will force the controller to run that zone in a STAN-
DARD Mode using setpoint set by function [36]. This allows a mix of
zones running STANDARD Mode and PROFILE
33
6.8
Function Group [75] Ramp and Soak
Function [75] controls segment functions [01] to [20]
On entering function [75] the function display shows 75. The upper
display will read 01 . The zone window will show 1.
To select the segment and zone to be set, enter the segment number and
zone. Note that the segment number is restricted by the number of
segments set in function [74].
To increment the flashing digit press the button
To advance to the next digit (segment and zone number) press the
button
To enter the segment to be set press the button
On entering segment display will advance to the next segment. If the last
segment of that zone is entered then display will advance to the first
segment of next zone.
To return to function [70] press two buttons and together
for a few seconds.
6.8.1
Function [01]
Set Segment 1
Setpoint
(9999) degrees
Slope
(99.9) deg / minute
Time
(99.99) hours
In function [01] the function display will show 01.
The zone display will show the selected zone.
The upper display will show the 4 digit current Setpoint. To accommo-
date 3 parameters the upper display will scroll through 3 independent
displays. To recognize which display is shown each parameter has a
different look. The setpoint parameter displays 4 digits. The slope
parameter is displayed with three digits. The time parameter is displayed
with 2 digits followed by 2 decimal digits.
To increment the flashing digit press the button
To advance to the next digit and scroll press the button
To save the segment and advance to the next segment press the button
To return to function [75] press two buttons and
together
for a few seconds.
34