3.6 Sensor Placement
Proper sensor placement is essential. It can eliminate many problems in
the total system. The probe should be placed so that it can detect any
temperature change with little thermal lag. In a process that requires
fairly constant heat output, the probe should be placed close to the
heater. In processes where the heat demand is variable, the probe
should be close to the work area. Experimenting with probe location
can often provide optimum results. Some units are shock sensitive and
require care in handling and installation. To avoid current feedback from
zone to zone and from zone to RS-232 communications, ungrounded
thermocouples are recommended. Thermocouple wires should not be
placed in the same conduit as the power lines.
120V Jumper
Placement:
240V Jumper
Placement:
LINE
120VAC
LINE
240VAC
!
WARNING! !
Line Voltage
see Pg 16
17
3.5 Changing Line Voltage Setting
Program the input line voltage by placing jumpers on the line plug as
shown:
SECTION 4
PARTS OF THE INSTRUMENT
Temperature Scale Selection
Zone
Temperature\Setpoint Display
Function Setting
Set\Shift\Reset Button
Advance Digit Button
º
Function
Temperature\Setpoint Display- Main display with multiple
functions.
Temperature Scale Selection- Choice of °C or °F.
Function Setting- Indicates the operating status of the instrument.
Zone Setting- Indicates an active zone or a zone that is being set.
Set\Shift\Reset Button- Used to select digits during setup or to
unlock the display scan.
Advance Digit Button- Used to increment selected digit.
Load Button- Used to accept a setting or to lock display zone.