![background image](http://html1.mh-extra.com/html/omega/c9000a-series/c9000a-series_user-manual_737594045.webp)
39
FUNCTION
(Op#).(Fn#)
Parameter/Comment
0.26
100% x max output
1.26
95%
2.26
90%
3.26
85%
4.26
80%
5.26
75%
6.26
70%
7.26
65%
8.26
60%
9.26
55%
10.26
50%
11.26
45%
12.26
40%
13.26
30%
14.26
20%
15.26
10%
TABLE 3-6
ADVANCED FUNCTIONS.26 -.50
NOTE
.26 HEATING OUTPUT LIMIT (OUTPUT 1)
These Advanced Functions, .26 through .50,
are not required for day-to-day use. They
should
not
be accessed except during set-up
by qualified personnel.
Allows adjustment of maximum output to heater in percent.
Example: if 50% (Option 10) is selected, then the output of the
controller would never be allowed to be greater than 50%. This
might be used with an oversized heater. Autotune can not be used
with SP1 heat limit other than 100% (Option 0). Example: with 10
second cycle time 50% (Option 10) would never allow more than 5
sec on 5 sec off when controller calls for 100% output. Not
applicable if SP1 is ON/OFF.
Содержание C9000A SERIES
Страница 6: ...This page is intentionally blank iv ...
Страница 76: ...70 NOTES ...
Страница 85: ...79 DIMENSIONS WITH POWER SOCKET See Figure 8 1 below Figure 8 1 Dimensions with the Power Socket ...
Страница 90: ...84 NOTES ...