30
Controller detects a break in the control loop caused by a sensor
short or heater break. This is the amount of time the controller will
wait for the control action to have an affect before an error
message is given (EE3). Not recommended for control around
ambient temperature. Option 14 is recommended for typical
applications (two times integral time). Refer to Section 4.2.
TABLE 3-4 (Cont'd)
FUNCTION
.12 LOOP BREAK ALARM TIME
(Op#).(Fn#)
Parameter/Comment
0.12 OUT
1.12
1 min
2.12
2 min
3.12
4 min
4.12
6 min
5.12
8 min
6.12
10 min
7.12
15 min
8.12
20 min
9.12
30 min
10.12
40 min
11.12
50 min
12.12
70 min
13.12
90 min
Recommended initial setting:
14.12
2 x Operational Integral Time
.13 ACTIVATE ADVANCED FUNCTIONS .26-50
.14 NOT USED
Advanced Functions to be selected at initial setup by qualified
personnel
only.
Press
★
for 5 seconds to access Advanced Functions .26-.50.
CAUTION