45
ERROR APPLICATION
CODE
PROBLEMS
ACTION
RESET
EE1
Sensor burnout
Check sensor
Self clearing
EE2
RTD/Pt 100 short Check sensor
Self clearing
EE3
LBA Loop break
Check control
Latches: Reset
loop
Autotune AT/PT tuning cycle problems
Autotune run aborted: Previous values retained
EE5
Outside time limit
Latches: Reset
EE6
Overshoot exceeds limit
Latches: Reset
EE7
Unable to run Autotune,
Latches: Reset
SP1 in ON/OFF mode
Software problems
EE8
Calibration data
Replace CN9000A See next page
error
if it persists
EE9
System error
Replace CN9000A See next page
if it persists
H
Unit in
If Manual Mode
Reset to 0.0
Manual Mode
not desired,
for normal
check Function .0
operation
SECTION 4 DIAGNOSTICS
4.1FAULT INDICATION
Depending on the selection made at Functions .20 and .21, the
SP1 and SP2 outputs are turned ON or OFF if sensor is open. The
main temperature display, on a fault indication, is replaced by "EE"
flashing, followed by a digit. This indicates that an error has been
detected in the system. Action should be taken as follows: