47
Selecting LBA-EE3 message only:
1. Step to Function .12-LBA time Option 0-LBA OUT, displayed.
2. PRESS
★
to change to option.
3. PRESS
to select Option 14, the recommended initial setting
(2 x the control band in use).
4. In the LBA alarm condition, EE3 is displayed alternating with
process temperature. The alternating EE3 display latches until
reset. To reset, Press
simultaneously.
To configure Alarm relay SP2 to LBA:
Select Option 6 in Function .19 (Relay latches in alarm
condition, to reset, Press
simultaneously).
NOTE
Reset EE3/Relay before any other program changes.
Used to assist with machine operation and troubleshooting.
Monitors and displays minimum and maximum temperatures, and
variance (deviation) to 0.1°C/°F.
Displayed temperatures are measured values, independent of
setpoint. This high sensitivity monitor may be affected by
interference. (Use a snubber to minimize disturbance).
4.3 OPERATIONAL DIAGNOSTICS
4.3.1 Diagnostics (Functions .38 -.49)
effect of
load change
ie min
Temperature
setpoint
Overshoot
Variance
Min/max.
max - SP
overshoot
to 0.1
Figure 4-2. How to use Functions .38 -.41
Time