Configuring the Alarm Dialer
The OMA-D560 system continually monitors all inputs for alarm set-points that have been violated. If a set-
point has been exceeded for a designated period of response time, the OMA-D560 system recognizes this as the
existence of an alarm condition.
It will send the message to up to eight designated telephone numbers anywhere on or off site and at any time. If
the calls are unanswered, the OMA-D560 system will wait a pre-set length of time and perform the complete
dial-out sequence again.
The alarm dial-out sequence will continue
−
even if the alarm condition has cleared
−
until the alarm has been
externally acknowledged.
To fully configure the alarm dialer, use the
INP S
command to set the alarm set-points and the
PHO O
command to program the dialing directory (refer to the Alarm Handling and Command Reference sections).
Configuring the Output Controller
The OMA-D560 system can automatically control loads in response to input set-points or alarm conditions.
To configure the output controller, use the
INP S
command to set the control set-points and the
OUT S
command to define the control mode (refer to the Output Control and Command Reference sections).