30
OMEGA ENGINEERING, INC.
Help with the POW Command
Type POW at the command prompt and the OMA-D560 system will return a list of valid power monitoring
commands and related instructions.
COMMAND>POW
SYSTEM POWER FUNCTIONS
------ ----- ---------
POW R Power Status Report
POW S Set/Check Power Settings
Power Status Report
This enables you to report the current condition of the AC line power that is supplying operating voltage to the
OMA-D560.
COMMAND>POW R
AC POWER REPORT
== ===== ======
AC Power is On
Power Failure Alarm Parameters
Change alarm parameters associated with the AC line power.
COMMAND>POW S
SET/CHECK POWER SETTINGS
--------- ----- --------
1 = Set AC Fail alarm
2 = Alarm response time
0 = Previous Menu
Choose a Number>
Power Alarm
When enabled, the OMA-D560 system will begin an alarm sequence when the power has been off for the
specified alarm delay time.
Power Alarm Delay
The power must be off continuously for this amount of time before a power alarm is recognized. A time
period of 5 to 15 minutes is recommended in most cases to prevent alarms during momentary outages.
Enter a much smaller time if you are monitoring power sensitive devices but set it much higher if the
location is prone to long power outages and the equipment you are monitoring would not be affected.