Operation
Reports
The OMA-D560 generates a variety of concise text reports. Each report is updated just prior to generation and is
time-stamped. An auto-report feature, when enabled, produces an input report at the beginning of each
communication session without the need to enter a pass code. Reports can be accessed by any security level.
Input Report
To get a report of the present condition of the eight inputs, including any that may have exceeded an alarm set-
point, type INP R at the command prompt.
Analog inputs will provide LO, HI, and OK status; discrete will provide AL and OK indicators.
COMMAND>INP R
INPUT STATUS REPORT
----- ------ ------
#1 mA OK 4.000
#2 mA OK 4.000
#3 mA OK 4.000
#4 mA OK 4.000
#5 Swtch OK ON
#6 Swtch OK ON
#7 Swtch OK ON
#8 Swtch OK ON
Time: 02/05/00 12:52:21
Output Report
To get a report of the present condition of the four outputs, type OUT R at the command prompt.
COMMAND>OUT R
OUTPUT STATUS REPORT
------ ------ ------
#1 Relay MANUAL OFF
#2 Relay MANUAL OFF
#3 Relay MANUAL OFF
#4 Relay MANUAL OFF
Time: 02/05/00 12:53:56
Alarm Report
To get a report of all alarms, including those that have not yet been acknowledged, type ALM R at the
command prompt.