25
www.omega.com
COMMAND>INP
INPUT FUNCTIONS
----- ---------
INP R Input Status Report
INP O Input Filtering Options
INP S Set/Check Input Settings
Input Status Report
To get a real-time report of the present condition of the eight inputs, including any that may have exceeded an
alarm set point, type INP R at the command prompt.
Analog inputs will provide LO, HI, and OK status; discrete will provide AL and OK indicators.
COMMAND>INP R
INPUT STATUS REPORT
----- ------ ------
#1 mA OK 4.000
#2 mA OK 4.000
#3 mA OK 4.000
#4 mA OK 4.000
#5 Swtch OK ON
#6 Swtch OK ON
#7 Swtch OK ON
#8 Swtch OK ON
Time: 02/05/00 15:22:39
Input Operation Parameters
Type INP O at the command prompt to get a sub-menu parameters (applied globally to all inputs) that affect the
sensitivity and responsiveness of the monitored inputs.
Input Damping
Input damping causes the OMA-D560 to react slowly to a rapidly changing input. For example, if
temperature were being monitored and the temperature probe was moved from an ice bath to a hot water
bath, a damped input would show a gradual change in temperature every 10 to 20 seconds, rather than an
instantaneous change. This option will eliminate many false alarm situations.
COMMAND>INP O
INPUT FILTERING OPTIONS
----- --------- -------
Input filtering is disabled
Change present state ?
Type Y or N
Input Setup Parameters
Type INP S at the command prompt to control the configuration parameters for each input. You will get a list
of all configurable inputs. Select the input you wish to configure and you will get a sub-menu containing
parameters for that input.