TROUBLESHOOTING 

FAULT 

PROBABLE CAUSE  

ACTION 

THE PANEL REPORTS: 

«

PANEL 

DISCONNECTED 
BATTERY

»

 

The internal battery of the panel is not 
connected 

Connect the battery. 

THE PANEL REPORTS: 

«

POINT 

Χ

,WRONG 

LUMINARY

»

 

 

1)

 

The luminaire type was changed in 
the specific address. 

2)

 

During the first detection, the 
luminaire was OFF. 

Re execute the automatic point 
recognition via the technician menu 
(SYSTEM > FIND ALL POINTS), or 
install manually the luminaire type 
via the option POINTS. 

THE PANEL REPORTS: 

«

POINT 

Χ

, LUMINARY 

COMM.

»

 

 

 

1)

 

The luminaire is probably OFF 
(without battery or 230V power) 
or there is an internal 
malfunction.  

2)

 

Probable noise on the 
communication line due to nearby 
electromagnetic interference.  

3)

 

Bad communication due to long 
distance and small cable cross 
section. 
 

Verify the good operation of the 
luminaire. Inspect for internal faults 
such as disconnected wiring.  
Check for probable nearby 
electromagnetic interference. 
Verify the specifications of the 
communication cable. 

THE PANEL REPORTS: 

«

POINT 

Χ

LAMP/BATTERY 
FAULT

»

 

As mentioned, the error comes from 
either an unconnected battery or a 
lamp/led error. 

Inspect for probable faults or 
insufficient connection at the 
specified points. 

THE PANEL REPORTS: 

«

OUTPUT 

Χ

, SHORT 

CIRCUIT

»

 

There is a short circuit along the 
length of the loop / communication 
line. 

Disconnect the output terminal 
block and inspect for probable short 
circuits along the line connect on the 
specific output.  

THE PANEL REPORTS: 

«

POINT  

Χ

DISCONNECTED

»

 

The panel can

t detect a luminaire that 

was previously registered. 

Inspect for probably disconnection 
at the specific point. 

THE PANEL REPORTS: 

«

POINT X, NOT 

REGISTERED

»

 

The point has been detected after 
automatic point recognition but is not 
registered in memory. 

Conduct automatic point recognition 
or manually install the point. 

THE PANEL REPORTS: 

«

POINT X, BATTERY 

CAPACITY FAULT

»

 

During the last duration test of the 
luminaire a problem was found. The 
real duration is smaller that the stated 
duration. 
 
 
 

Replace the luminaire battery with 
one of the same type and rating.  
(see the luminaries user manual)  

Содержание GR-6500

Страница 1: ...1 923650001_90_004 Emergency lighting addressable panel GR 6500 Quick Installation Guide Generic Design LIGHTING ADR...

Страница 2: ...h the corresponding Olympia Electronics addressable luminaires NEEDED MATERIALS Mounting Hardware Screwdrivers Multi meter Pliers Cutter MAINTENANCE The periodical checks must follow the EN50172 or be...

Страница 3: ...500 can support up to 250 points The maximum connected points to each LOOP must not exceed the 150 Each point must have unique non repeatable address No arithmetic address sequence is obligatory Keep...

Страница 4: ...and no additional unused conductors Select shielded cable for every installation The cable shield must be reconnected in every cut during the length of the loop and must be terminated to the PE Power...

Страница 5: ...opology Note Max 250points in total Point 1 Point 2 Point 3 Point 4 Point 5 L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L Z 1A Z 1B Point Point Point Point Point Poin...

Страница 6: ...st Connect the each zone to the corresponding output of the panel Connect the monitoring Relays Optional Connect the 12V 7Ah Lead Acid battery with the correct polarity ACTIVATION Make sure there is n...

Страница 7: ...et through the panel connecting and setting the luminaires one by one ADDRESSING LUMINAIRES TECHNICIAN MENU SETTINGS CHANGE ADDRESS POINT Note It is not required to connect the 230VAC power on the lum...

Страница 8: ...the panel TECHNICIAN MENU POINTS Assign a Zone for each point Optional TECHNICIAN MENU Program FUNCTION TEST TECHNICIAN MENU Program CAPACITY TEST TECHNICIAN MENU NETWORK Set ETHERNET PCB Enable or Di...

Страница 9: ...Verify the specifications of the communication cable THE PANEL REPORTS POINT LAMP BATTERY FAULT As mentioned the error comes from either an unconnected battery or a lamp led error Inspect for probabl...

Страница 10: ...o the address where the problem is By repairing the connection problem on point we can now see only GOOD packets increasing we can see the name of the luminaire as well as the battery voltage and char...

Отзывы: