THE PANEL FINDS
ONLY CERTAIN
LUMINAIRES
1)
There is an open circuit in the
communication line. If the
connection is done using the loop
topology then there might be
more than one open circuit.
2)
Another cause might be wrong
addressing of non detected points.
Find the open circuit, between the
last detected point and the first un
detected. To easily see the
communication indication go to
MENU>TEST>POINTS IN TEST
and by
using the up/down arrows go to the
address where the problem is. By
repairing the connection problem,
on point
Χ
we can now see only
«
GOOD
»
packets increasing, we can
see the
name of the luminaire
as
well as the battery voltage and
charge or lamp current.
(any connection open circuit can be
located in section 5, CABLE
INSPECTION)
If there is no open circuit then test
for wrong addressing.
THE PANEL REPORTS:
«
POINT
Χ
, CONFLICT
DATA
»
The panel detects more that one
points with the same address.
Inspect the adjusted addresses for
errors. The point that can
’
t be
recognized in the desired address via
the operation
MENU>TEST>POINTS IN TEST
as
mentioned above probably has a
conflicting address with another
point.