MOUNTING THE PANEL
•
The panel must be installed in a suitable area and must not be obscured. Also it must be
powered by a permanent 230V power connection from the fuse panel and not via a power
outlet or a wall switch.
PREREQUISITE REQUIREMENTS AND PRELIMINARY PROCEDURES
Addressable Luminaire Connections
•
16 available Zones.
•
The GR-6500 can support up to 250 points.
•
The maximum connected points to each LOOP must not exceed the 150.
•
Each point must have unique non repeatable address.
•
No arithmetic address sequence is obligatory.
•
Keep a record of points
’
addresses and names.
Mo u n t in g H o le s
Ba t t e r y co mp a r t me n t
A- 9 8 6 ( 1 2 V/ 7 Ah Pb )
BMS r e la y
Ge n e r a l o u t p u t s
( Sir e n s, o p t ica l in d ica t o r s - 2 4 V/ 0 . 3 A ma ximu m
)
F u se d t e r min a l b lo ck ( 2 2 0 - 2 4 0 V AC )
F u se T
V
0 . 6 3 Α/ 2 5 0
Mo u n t in g h o le
C o mmu n ica t io n o u t p u t s
Z 1 A, Z 1 B, Z 1 C , Z 1 D
Min i U SB