ENGLISH
EN - 30
At this point the current configuration of the machine will be displayed for a few moments as indicated below:
LED A
(red) on: appliance fitted with heat pump function;
LED B
(green) on: installation to the lower part of the wall (to the ground) (factory installation);
LED C
(yellow) on: installation to the upper part of the wall (to the ceiling);
LED D
(green) on: reset settings function after an active black-out (factory setting).
Then, all of the LEDs on the console will start flashing simultaneously for 10 seconds.
During this phase, it is possible to change the previously displayed setting related to the type of installation
of the equipment by means of the micro key.
Configuration of the electronic control for installation to the upper part of the wall determines an
automatic correction of the room temperature detected of 3°C.
At this point the self-diagnostic function activates the appliance in heating mode (if fitted with the heat pump
function) for approx.2 minutes and then in cooling mode for another 2 minutes.
it is possible to terminate the function prematurely simply by switching the appliance off using the remote
control.
Should the conditioner block and signal an error, specify the LEDs that are flashing to the service centre in
order to facilitate the intervention.
DESCRIPTION
LED D
GREEN
LED C
YELLOW
LED B
GREEN
LED A
RED
UniCo unit internal exchanger overtemperature (Hti)
off
off
on
off
UniCo unit external exchanger overtemperature (Hte)
off
off
on
on
UniCo unit outdoor temp. probe fault (short circuit) (tfS7)
off
on
off
off
UniCo unit outdoor temperature probe fault (open circuit)
(tfS8)
off
off
off
on
UniCo unit internal fan malfunction (Sv)
off
on
off
on
UNICO unit insufficient exchanger temperature (CF/RL)
off
on
on
off
UniCo unit condensation water maximum level (of)
off
on
on
on
UniCo unit eeprom parameters not valid (CKS)
on
off
off
off
UniCo unit ambient temperature probe fault (short circuit)
(tfS1)
on
off
on
off
UniCo unit ambient temperature probe fault (open circuit)
(tfS2)
on
off
on
on
UniCo unit internal exchanger temperature probe fault
(short circuit) (tfS3)
on
on
off
off
UniCo unit internal exchanger temperature probe fault
(open circuit) (tfS4)
on
on
off
on
UniCo unit external exchanger temperature probe fault
(short circuit) (tfS5)
on
on
on
off
UniCo unit external exchanger temp. probe fault (open
circuit) (tfS6)
on
on
on
on
SPlit unit malfunction
on
off
off
on
:
flashing
Содержание Unico Twin
Страница 2: ......
Страница 7: ...2 3...
Страница 8: ...min 300mm 8mm min 1500mm 8 6 9 7 H 6a N M Y 4 5...
Страница 9: ...10 202 mm G 162 mm 130 mm G 12 11 G F D F G 13 14...
Страница 10: ...6mm 15 19 17 16 20 18 F E E E...
Страница 11: ...21 H L1 L H A A1 H L L1 24 22 23 L...
Страница 12: ...28 29 max 43mm 26 27 25 Wd Wh We Wf Wc Wb Wg Wa Wi Wc Wb Wa...
Страница 13: ...L G N B A 34 32 33 35 J1 J2 P1 P1 21 22 23 P2 30 31 X1 X2...
Страница 14: ...36 CLICK 40 8m 8m 37 38 39 10...
Страница 15: ...AUTO OFF 43 42 41 3 F 40a 40b 40c...
Страница 16: ...44 45 F1 F2 F1 F2 46 L N G B A POWER TO MASTER...
Страница 247: ......
Страница 248: ...262286A...