The heated optics can be set to one of the following:
•
Not operated
•
On continuously
•
Automatic, per temperature change (default): you can define the start temperature
below which the window is heated. (The default is 68°F (20°C).) This temperature can
be defined between 32°F (0°C) to 122°F (50°C). The heating stops when the
temperature is 27°F (15°C) above the start temperature.
For more information, see
Configuring your Detector
on page 29.
1.4.3
HART Protocol
The 40/40 Flame Detectors use the HART Protocol.
HART Communication is a bi-directional industrial field communication protocol used to
communicate between intelligent field instruments and host systems. HART is the global
standard for smart process instrumentation and the majority of smart field devices
installed in plants worldwide are HART-enabled.
HART technology is easy to use and very reliable.
Through the HART connection, you are able to perform:
•
Detector set-up
•
Detector troubleshooting
•
Detector health and status
For more details, refer to the
HART Manual TM 777030
.
1.4.4
RS-485 Modbus
For more advanced communications, the 40/40 detector has an RS 485 Modbus-
compatible output that provides data communication from a network (up to 247 detectors)
to a host computer or universal controller for central monitoring. This feature allows for
reduced installation costs, easy maintenance and local or remote diagnostic tools.
1.4.5
Product Certification
1.4.5.1
ATEX, IECEx
The 40/40I Flame Detector is certified to:
•
ATEX Ex II 2 GD per SIRA 07ATEX 1149 and IECEx SIR. 07.0085.
•
EExde IIB + H
2
:
•
T5 Ambient Temp. -55°C to +75°C.
•
T4 Ambient Temp. -55°C to +85°C.
This product is suitable to use in hazardous zones 1 and 2 with IIB + H
2
gas group vapors
present.
1.4.5.2
FM, CSA
The 40/40I Flame Detector is certified to FM and CSA Explosion Proof per:
•
Class I, Division 1, Groups B, C and D, T5 Ta = 85°C.
•
Dust Ignition Proof – Class II/III Division 1, Groups E, F and G.
•
Ingress Protection – IP67, IP66, NEMA 250 Type 6P.
•
Fuel Test Response including: Gasoline, N-Heptane, Diesel, JP5, Kerosene, Ethyl,
Alcohol 95%, IPA, Methanol, Methane, LPG, Polypropylene, and Paper.
•