14
1.5.1.3
Other Fuels
The detector reacts to other types of fire as follows:
•
The baseline fire refers to n-heptane 1ft
2
(0.1m
2
) and is defined as 100% sensitivity.
•
For fuel fire – standard pan fire size: 1 ft
2
(0.1 m
2
).
•
For gas flame - 20 inch (0.5m) high, 8 inch (0.2m) width plume fire.
•
Maximum Response Time: 10 sec.
Table 3: Fuel Sensitivity Ranges
Type Of Fuel
Percent of Max. Distance at each Sensitivity
Range
Gasoline
100%
N-Heptane
100%
JP4
70%
Kerosene
70%
Diesel Fuel
70%
Alcohol 95%
60%
IPA
60%
Methanol
55%
Methane
45%
LPG
45%
Paper
35%
Polypropylene
15%
1.5.2
Cone of Vision
•
Horizontal
: 100°
Figure 1: Horizontal Field of View
Содержание SharpEye NP40IGB
Страница 1: ...Ref NP40IGB REV A Nov 2009 USER GUIDE...
Страница 35: ...36 Appendices...
Страница 49: ...50...
Страница 50: ...51...