33
3.3.1
Automatic BIT Test
Check that the indicators show normal conditions. See
Powering Up
on page 31.
3.3.2
Manual BIT Test
Important
: If the function setup
Alarm BIT
and/or
Auxiliary BIT
are set to
Yes
(default
No
), the Alarm, Auxiliary Relay and 0-20mA outputs are activated during a Manual BIT.
Therefore, automatic extinguishing systems or any external devices that may be activated
during BIT
must
be disconnected.
Ø
To perform a Manual BIT:
27
Verify that the detector is Normal Mode.
28
Initiate Manual BIT. The results of successful and unsuccessful
manual BITs are detailed in Table 12 and Table 13.
3.3.3
Testing with Fire Simulator Model 20/20-310
The Fire Simulator Model 20/20-310 can be used to simulate exposure of the detector to a
real fire condition. The detector is exposed to radiation at the required detection level. As
a result, the detector will generate a Fire Alarm signal. See
Long Range IR3 Fire
Simulator
on page 44 for more information.
Important: If the detector is exposed to a fire simulator, the Alarm and Accessory
Relays and 4-20mA are activated during the simulation. Therefore, automatic
extinguishing systems or any external devices, which may be activated during this
process, must be disconnected.
Ø
To perform Fire Simulator Test:
29
Power up the system and wait up to 60 seconds for the detector to turn to a normal
state. The Power LED turns on.
30
Aim the Industrial Scientific Fire Simulator Model 20/20-310 at the target point of the
detector (Figure 14), in a way that the radiation emitted by it is facing directly towards
the detector. (See
Long Range IR3 Fire Simulator
on page 44).
31
Press the operation button once. After few seconds, a successful test shows the results
shown in Table 21.
Table 21: Results of Successful Fire Simulator Test
Component
Action
Notes
4-20mA
Turn to 15mA
For a few seconds and then return to 5mA
Alarm Relay
Activated
for a few seconds and then returns to Normal
Auxiliary Relay
Activated
for a few seconds and then returns to Normal
Fault Relay
Remains active
during the test
LED
Red, steady
The detector is now ready for operation.