© 2019 OJ Electronics A/S

TECHNICAL DATA

 

Power consumption .................................. 0.5 W
Output ......0-10 V=, 2-10 V=, 0-20 mA, 4-20 mA
Measuring range, pressure ................. 0-2500 Pa
Accuracy * .........................0.5% *MV ± 2.5% Pa
Maximum pressure ...................................20 kPa
Maximum load
0 – 10 V= ................................................. >2.5kΩ
0 – 20 mA ...............................................<=450Ω
Housing dimensions (h×w×d) ... 91 × 75 × 38mm
Cable dimension ................................. ø3-10 mm

Connection

VCH-3202-DI, 

......4 x Screw term,

max. 1.5 mm²

Pressure tubes ................................ 2 × ø6,2 mm

Environment data

Operating temperature ........................................

-20°C to +40°C (continuous) **

Operating humidity ...............10%RH to 95%RH, 

non-condensing

Operating altitude ...................................≤2000m
Enclosure rating ............................................IP54
Weight ........................................................110 g

*

Note: MV stands for Measured Value

** Note: Ambient temperature affects the LCD 
display speed and contrast

SERVICE AND MAINTENANCE

VCH-x2xx-DI contains no components which 
require service or maintenance. 
Please contact your supplier if faults arise.

DISPOSAL AND ENVIRONMENTAL  
PROTECTION

Help protect the environment by disposing of 
the packaging and redundant products in a 
responsible manner.

Product disposal

Products marked with this symbol 
must not be disposed of along with 
household refuse but must be deliv-
ered to a waste collection centre in 
accordance with current local  regula-
tions.

OJ Electronics A/S

Stenager 13B · 6400 Sønderborg · Denmark
Tel. +45 73 12 13 14 • Fax +45 73 12 13 13
[email protected] • www.ojelectronics.com

CE MARKING
Regulations

OJ Electronics A/S herewith declares that the 
product is in conformity with the following direc-
tives of the European parliament:
LVD - Low Voltage Directive
EMC - Electromagnetic Compatibility
RoHS - Restriction of the use of certain Hazard-
ous Substances
WEEE - Waste Electrical and Electronic Equip-
ment directive

Applied standards

EMC emission  

EN 61000-6-3

EMC immunity 

EN 61000-6-2

TROUBLESHOOTING

Symptom

Cause

Action

Fluctuations at output

P-band or I-time set to low

Enter higher values at the P-
Band or I-time menu

Front LED toggles between red 
and green

Greater fluctuation than the 
Dead band allows

Raise the value at the Dead 
band menu

Error code E101 displayed

Pressure element out of range

Check for clogged filters

Error code E102 displayed

Pressure element temperature 
out of range

Check external heating or cool-
ing units

Error code E103 displayed

Pressure element defective

Replace VCH

Negative measured value 
displayed

Tubes interchanged

Exchange tubes on plus (+) and 
minus (-) tube connectors

Measurement deviation

VCH positioned where tem-
perature is out side specified 
temperature range

Adjust ambient temperature to 
range specified in these instruc-
tions

No or reduced pressure at 
measuring point

Check that pressure measure-
ment tubes are correctly fitted

Zero pressure at measuring 
points

Check connection to fan

Zero point deviation

Zero calibration not carried out

Depressurise VCH, if neces-
sary by removing both pressure 
tubes and carry out zero 
calibration

 

2

Supply voltage

 

...............24V~/= ±15%, 50/60 Hz

Содержание VCH-3202-DI

Страница 1: ...the K factor Mini mum k factor is 0 001 and maximum k factor is 9999 Please see the conversion table on page 7 for help to calculate the k factor The dot position shall be set before entering the valu...

Страница 2: ...ics A S herewith declares that the product is in conformity with the following direc tives of the European parliament LVD Low Voltage Directive EMC Electromagnetic Compatibility RoHS Restriction of th...

Страница 3: ...onsigne de la pression Versions avec plusieurs points de consigne Choisir le nombre de points de consigne et param trer les valeurs pour chacun Le minimum est 0 Pa et le maximum 2500 Pa Menu R gulateu...

Страница 4: ...es mati res dangereuses DEEE Directive propos des d chets d qui pements lectriques et lectroniques Normes appliqu es mission CEM EN 61000 6 3 Immunit CEM EN 61000 6 2 SERVICE ET ENTRETIEN Le VCH ne co...

Страница 5: ...Proportional band 0010 1000 Integrator time 0001 9999 sec Out Return to parent menu Analog output type 0 10V 0 20mA 2 10V 4 20mA Damping 01 30 sec Flow setpoint 0000 9999 Flow range 0000 9999 First s...

Страница 6: ...d the result k2 is entered into the VCH Example of calculation The k factor data for the equipment is declared to be 5 6 based on liter per seconds l s You want the VCH to handle ow in cubicmeters per...

Страница 7: ...imensioned drawing BR956B02b Fig 3 Position of measurement tube in relation to bends and branches BR1032A002a VCH BR1032A001a BR1032A012a Fig 4 Wiring diagram VCH 3202 DI Pressure Connection 1 2 3 4 V...

Отзывы: