• English

• Français

English

LIST OF FIGURES

The following figures are located at the back of 
the instructions:
Fig. 1:  Menu scheme
Fig. 2:  Dimensioned drawing
Fig. 3:   Position of measurement tube in relation 

to bends and branches

Fig. 4:  Wiring diagram 

Fig. 5:  Example of application
Fig. 7:  Orientation of VCH

INTRODUCTION

VCH-32x2-DI is electronic pressure/air controller 
with integrated regula-tor output, and is 
primarily used to control ventilation systems, eg. 
roof ventilators using either constant pressure or 
constant flow. VCH-32x2-DI is designed for 
controlling fans with analog interface. 

:LWK

 semiconductor pressure element with no 

air throughput, thus protecting the unit from 
dust in the ventilation system. The pressure 
element is temperature compensated to provide 
accurate pressure measurement throughout the 
specified temperature range. See ‘Technical 
Data’.

INSTALLATION

VCH-x2xx-DI should be attached to a firm, level 
surface using two screws. The pressure 
controller also functions with only one tube fitted 
to the tube connectors (+ or -). However, two 
tubes should always be fitted to maintain the 
enclosure rating.
Pressure is supplied to the measurement unit by 
tubes, the higher pressure being connected to 
the ‘+ tube connector’ and the lower pressure to 
the ‘÷ tube connector’ (see fig. 4). 
The pressure tubes must be as short as pos-
sible and must be secured in position to prevent 
vibration. 
To obtain the best possible results, pressure 
must be measured where there is least risk of 
turbulence, i.e. in the centre of the ventilation 
duct and at a distance of at least twice the width 
of the duct from bends and six times the width 
from branches (see fig. 3).

The housing is opened without the use of tools 
by pressing the snap lock beside the tube con-
nectors.

Analog cable connection (VCH-3202-DI)

The output from the VCH is either voltage or 
current controlled. The VCH must be provided 
with a 24 VAC/DC power supply, see figure 4.

Setup menu

Use the buttons 

 , 

 and  

OK 

to navigate 

the menu. The buttons can be found on the 
backside off the lid. The menu is divided into 
three parts - Setup [ Set ], Regulator [ Reg ] and 
Calibration [ CAL ]. Follow the menu scheme in 
figure 1 from the bottom up. Note some settings 
may be hidden depending on other selections.

Setup - Pressure or flow mode 

[  

]

Use Setup menu 1 to choose between Pressure 
or Flow mode. 

Setup - Pressure range 

 ]

Use Setup menu 2 to enter the pressure range.
Set the Pressure range to match the system 
pressure working range.

Setup - Pressure setpoint 

 ]

Use Setup menu 3 to enter the pressure set-
point. 
Versions with several setpoints: Choose the 
number of setpoints and setup the values for 
each one.
Minimum is 0 Pa and maximum is 2500 Pa. 
Setting the minimum setpoint to 0 will halt the 
ventilation.
The setpoint has to be lower than the Pressure 
range.

Setup - k-factor 

 ]

Use Setup menu 4 to enter the K-factor. Mini-
mum k-factor is 0.001 and maximum k-factor is 
9999. Please see the conversion table on page 
7 for help to calculate the k-factor. The dot 
position shall be set before entering the value. 

Setup - Flow range 

 ]

Use Setup menu 5 to enter the flow range. Set 
the Flow range to match the system flow work-
ing range. The dot position shall be set before 
entering the value. The selected dot position 
will also apply to the display, when showing the 
current flow.

Setup - Flow setpoint 

 ]

Use Setup menu 6 to enter the air flow setpoint. 
Versions with several setpoints: Choose the 
number of setpoints and setup the values for 
each one. 
The scale is 0.000 to 9999. Setting the setpoint 
to 0 will halt the ventilation.
The setpoint has to be lower than the Pressure 
range.

 ]

Setup - Damping 

[  

]

Use Setup menu 7 to enter the damping. 
Minimum damping is 1 seconds and maximum 
damping is 30 seconds. A low damping can 
result in unsteady readings, while a higher 
damping gives a more steady reading but also a 
slower response time for the regulation.

Setup - Analog output type 

[  

]

Use Setup menu 8 to enter the analog output  
mode. It is possible to switch between 0 - 10 
VDC, 0 - 20 mA, 2 - 10 VDC and 4 - 20 mA as 
regulator output.

Regulator menu

The VCH-x2xx-DI default PI values will fit most 
systems. Only change the values if it is required 
or for optimization needs.

Regulator - Integrator time 

[  

]

Use Regulator menu 1 to set the integrator time. 
Minimum integrator time is 1 second and maxi-
mum integrator time is 9999 seconds. A low 
value can make the system unstable and a high 
value can give a slow regulator response. 

Regulator - Proportional band 

[  

]

Use Regulator menu 2 to set the proportional 
band. Minimum proportional band is 10% and 
maximum proportional band is 1000% of the 
Pressure/Flow range.  A low value can make the 
system unstable and a high value can give a 
slow regulator response. 

Regulator - Dead band 

[  

]

Use Regulator menu 3 to set the dead band. 
Minimum dead band is 1% and maximum dead 
band is 50% of the Pressure/Flow setpoint  

 / 

 ]. If the regulator is used to control 

a damper, choose a higher value to avoid exec-
sive activity.

Regulator - Minimum regulator output 

Use Regulator menu 4 to set the minimum 
regulator output. Minimum regulator output can 
be set between 0% and 50%.

Regulator - Maximum regulator output 

 ]

Use Regulator menu 5 to set the maximum 
regulator output. Maximum regulator output can 
be set between 50% and 100%.

Calibration menu

When calibrating, make sure the VCH are in a 
pressure free environment. To obtain a pressure 
free enviroment remove the two air tubes on the 
VCH. For caution reasons, each calibration will 
only calibrate ±5 Pa.

Calibration 

 ]

Use Calibration menu 1 to calibrate. Confirm by 
pressing [ 

 ]. 

Factory reset 

 ]

Use Calibration menu 2 to set the VCH back to 
factory reset. Confirm by pressing [ 

 ].

LED INDICATOR

Front

A LED on the frontside of the VCH indicates 
the operating status. A constant red lit means 
the operating range is not reached. Contrary a 
constant green lit means the operating range is 
reached. A flashing red lit means that an error is 
active. See Troubleshooting for more informa-
tion. 

 

1

Содержание VCH-3202-DI

Страница 1: ...the K factor Mini mum k factor is 0 001 and maximum k factor is 9999 Please see the conversion table on page 7 for help to calculate the k factor The dot position shall be set before entering the valu...

Страница 2: ...ics A S herewith declares that the product is in conformity with the following direc tives of the European parliament LVD Low Voltage Directive EMC Electromagnetic Compatibility RoHS Restriction of th...

Страница 3: ...onsigne de la pression Versions avec plusieurs points de consigne Choisir le nombre de points de consigne et param trer les valeurs pour chacun Le minimum est 0 Pa et le maximum 2500 Pa Menu R gulateu...

Страница 4: ...es mati res dangereuses DEEE Directive propos des d chets d qui pements lectriques et lectroniques Normes appliqu es mission CEM EN 61000 6 3 Immunit CEM EN 61000 6 2 SERVICE ET ENTRETIEN Le VCH ne co...

Страница 5: ...Proportional band 0010 1000 Integrator time 0001 9999 sec Out Return to parent menu Analog output type 0 10V 0 20mA 2 10V 4 20mA Damping 01 30 sec Flow setpoint 0000 9999 Flow range 0000 9999 First s...

Страница 6: ...d the result k2 is entered into the VCH Example of calculation The k factor data for the equipment is declared to be 5 6 based on liter per seconds l s You want the VCH to handle ow in cubicmeters per...

Страница 7: ...imensioned drawing BR956B02b Fig 3 Position of measurement tube in relation to bends and branches BR1032A002a VCH BR1032A001a BR1032A012a Fig 4 Wiring diagram VCH 3202 DI Pressure Connection 1 2 3 4 V...

Отзывы: