© 2019 OJ Electronics A/S
k
2
= k
1
*
value (k-factor to enter into VCH-
-DI)
k
1
(k-fact
or given fr
om equipment)
m
3
/h
m
3
/h
l/s
l/s
m
3
/h x 1000
m
3
/h x 1000
l/s x 1000
l/s x 1000
m
3
/s
m
3
/s
cfm
cfm
0.278
3.6
0.001
3600
3600
1.699
1000
1000
0.472
1000
471.9
2119
2119
0.278
0.278
588.6
0.0036
1699
0.001
0.001
2.119
1000
0.589
K-factor conversion table (Flow only)
The k-factor given by the equipment (k1) is entered into the equation and the result (k2) is entered into the VCH.
Example of calculation:
The k-factor data for the equipment is declared to be 5.6 based on liter per seconds [l/s]. You want the VCH to handle flow in cubicmeters per hours [m³/h].
On the second row you will find the equations for k1 in [l/s].
In the first column you will find equations for k2 in [m³/h].
k2 = k1 * 3.6
k2 = 5.6 * 3.6
k2 = 20.16
Enter 20.16 into menu point Set4 [
]. Please remember to set the dot position before setting the value.
The VCH display will now show the calculated air flow in cubicmeters per hours. Remember to place the m
3
/h sticker on the VCH front.
k-Factor conversion table
BR1032A011a