![Ohkura RM10C Скачать руководство пользователя страница 46](http://html1.mh-extra.com/html/ohkura/rm10c/rm10c_instruction-manual_3527809046.webp)
―
45
―
HXPRM10mnC0001E
7.1.1 Setting the Range
(1)
Setting method
With a multirange system, setting the range for each channel is possible.
Use the
△
key to shift the mode
①
to
⑩
shown in the Table below.
Set the range from the following input signals. (mode
①
to
③
)
DC voltage
: ±10, 0 to 20, 0 to 50, ±200 mV DC, ±1, 0 to 5, ±10 V DC
DC current
: 4 to 20 mA DC (External shunt resistor: 250
Ω
)
Thermocouple
: B, R, S, K, E, J, T, C, Au-Fe, N, PR40-20, PL
Ⅱ
, U, L
Resistance temperature detector
: Pt100, JPt100
Set scaling, decade, square root, interchannel sum/difference/average. (mode
④
to
⑨)
Unnecessary channels can be skipped. (mode
⑩
)
Setting
Channel
Mode
Key
①
Voltage, Current
)
△
key
↓
↓
↓
↓
↓
↓
↓
↓
↓
②
Thermocouple
)
③
(
Resistance temperature detector
)
④
Scaling
)
⑤
Square root
)
⑥
Decade
)
⑦
Difference
)
⑧
Sum
)
⑨
Average
)
⑩
Skip
)
Setting for all
channels
[Note]
A decimal point position can be arbitrary setup only in the "scaling" and "square root" modes.
When you want to alter the decimal point position in Voltage/Current/Thermocouple/Resistance
temperature detector input set it in the "scaling" mode. To fix the decimal point position, set as
follows.
Input
Decimal Places
Input
Decimal Places
mV
±
1, 0
~
5V
±
10V
mA
2nd place
3rd place
2nd place
2nd place
***.**
**.***
***.**
***.**
Thermocouple
RTD
±
200mV DC
1st place
1st place
1st place
****.*
****.*
****.*