Calibration of Voltage
Conduct calibration in case of voltage, current or thermocouple input. For thermocouple input,
calibrate reference junction compensation together.
Conduct calibration according to the instructions in 7.2.12 Data Calibration (Calibration of the
voltage).(See page 82)
(2)
Calibration of Resistance Temperature Detector
Conduct calibration according to the instructions in 7.2.12 Data Calibration (Calibration of the
resistance temperature detector).(See page 83)
[Note]
A resistance value should not disperse greater than 6 m
Ω
from one wire to another.
When calibrate RTD for a channel, the input terminals of the other channels are shortcut.
Recording requires RTD calibration for every channel
[Note]
①
Calibrate at any one channel.
②
When a shunt resistor is attached to the input terminal block in case of current input, detach it
prior to calibration.
Wiring
Precision Voltage
(Current)
Generator
◯
+
◯
-
Digital Voltmeter
RM10C Recorder
Input Terminals
◯
+
◯
-
◯
+
◯
-
Precision Dial
Resistor
RM10C Recorder
Input Terminals