Mounting the PYROLINE® Con S BSK with a support system
Mounting version
C
– Uncut duct penetration
1
2
max. 2 cm
max. 100 mm
max. 100 mm
Abb 42:
Wall connection mounting version
C
1. Create a wall opening for the duct penetration.
Note!
Wall opening max. 2 cm > external duct dimensions.
2. Run the fire protection duct through the wall opening and mount it
1
,
see also 8.1 auf Seite 37 – 8.4 auf Seite 40.
Note!
The last suspension may be a maximum of 100 mm from the
wall.
3. Close the ring gap around the the duct with MIW-S mineral wool
2
.
4. Seal the mineral wool with non-combustible material, e.g. plaster.