35 | EN
Mounting instructions, PYROLINE
®
BSK fire protection duct
Mounting PYROLINE® Con D BSK on a wall/ceiling
Mounting version
B
– Uncut duct penetration
1
2
max. 2 cm
Abb 26:
Wall connection mounting version
B
1. Create a wall opening for the duct penetration.
Note!
Wall opening max. 2 cm > external duct dimensions.
2. Run the fire protection duct through the wall opening and mount it on
the wall
1
, see also „7.1 Kanalwanne montieren“ auf Seite 16.
3. Close the ring gap around the the duct with MIW-S mineral wool
2
.
4. Seal the mineral wool with non-combustible material, e.g. plaster.