36 | EN
OBO Bettermann
Mounting the PYROLINE® Con S BSK with a support system
8 Mounting the PYROLINE
®
Con S BSK with a
support system
The PYROLINE
®
Con S BSK fire protection duct is mounted with support
systems, which are mounted on the wall or the ceiling, depending on the
ambient conditions and wall structure. Wall brackets are mounted on the
wall, suspended supports with brackets are mounted on the ceiling or
threaded rods with support rails.
Danger of heavy components!
Fire protection ducts are very heavy and can cause serious injuries if they fall on
your head or other parts of the body.
Always work with a partner or work with mounting aids, such as scaffolding or a
mounting lift. Wear protective work clothing, such as safety shoes. If mounting
on the ceiling, wear protective helmets.
Note!
To achieve the maintenance of electrical function class E30, wall brack-
ets and brackets on suspended supports must have two suspension
points. They must therefore be additionally secured on connectors and
the ceiling with threaded rods. Alternatively, ceiling suspension can take
place with two threaded rods and a support rail.
≤ 1
00 mm
≤ 1
000
mm
Abb 27:
Support points, fire protection duct
The maximum distance between two brackets may be 1,000 mm. The
distance from the front end of a fire protection duct to the next bracket
may be a maximum of 100 mm.
WARNUNG