Operation
©2022 nVent
89217391 Rev. A
89
Screen contents:
Description
Low water
Fill mode
0 = manual OFF
1 = manual ON with pump OFF
2 = manual ON with pump ON
3 = automatic mode
Fill timeout
[s]
Maximum duration of the filling process until an error occurs.
Max. overfilling number
-
Maximum number of refilling processes in the specified time
interval.
System pr. warning
[bar]
Pressure warning, automatic refill starts
System pr. warning
hysteresis
[bar]
Hysteresis for the warning limit up to which the system will be
filled and the warning message will be cleared
System pr. error
[bar]
Pressure error, pumps continue to run
System pr. error hysteresis
[bar]
Hysteresis value (system pressure error)
Critical system pr. error
[bar]
Critical system pressure. When this value is reached, the pumps
will be switched off.
Critical system pr. error
hysteresis
[bar]
Hysteresis value (critical system pressure error)
Filling pump off-delay
[s]
Off-delay of the filling pump, i.e. the time during which the pump
continues to run after the hysteresis value has been exceeded.
Filling cycle monitoring
[days]
Time window in which the maximum number of automatic refills
will be monitored.